ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Acyclic services for Profibus DPV1
DPV1 error messages
319
12.6
DPV1 error messages
DPV1 error codes: application .................................................................................................. 319
DPV1 error codes: data access ................................................................................................ 319
DPV1 error codes: device ......................................................................................................... 320
DPV1 error codes: application-specific ..................................................................................... 320
DPV1 function 58 'Reason codes'............................................................................................. 320
5817
12.6.1
DPV1 error codes: application
5818
Error byte 1
Value [hex]
Meaning
A0 read
error
A1 write
error
A2 module
failure
A8 version
conflict
A9
feature not supported
AA user
specific
12.6.2
DPV1 error codes: data access
5825
Error byte 1
Value [hex]
Meaning
B0 invalid
index
B1
write length error
B2 invalid
slot
B3 type
conflict
B4 invalid
area
B5 state
conflict
B6 access
denied
B7 invalid
range
B8 invalid
parameter
B9 invalid
type
BA...BF user
specific