Operation
AS-i telegram errors on the master
431
14.9
AS-i telegram errors on the master
5960
We talk of a telegram error if the expected response telegram from a slave is not received within a
defined time or the signal sequences in the response telegram cannot be interpreted by the AS-i
master.
Examples
:
Due to an electrical fault the AS-i cable is used asymmetrically (one-sided earth fault). The AS-i
signal is no longer clearly recognisable.
The electrical AS-i connection to an AS-i slave is not OK.
The electrical environment of the AS-i system (EMC) interferes with the AS-i telegrams.
Here you cannot see in detail when which error occurred.
chapter Troubleshooting (
→
page
).
The error counter is reset...
- when the device is switched off and on again,
- with the function Reset error counter (
→
).
[MENU] > [Diagnostics] > Select master > [Telegr. Error]
MENU
0
USER
Step 1:
►
Press [Menu].
Quick Setup
PLC Setup
Slave Lists
OK
1
ESC
Step 2:
►
Press [ ] to scroll to [Diagnostics].
Slave Lists
Address Slave
Diagnostics
OK
1
ESC
Step 3:
►
Select [Diagnostics] with [OK].