ifm
Device manual AS-i M4 Gateway Profibus DPV1 (AC1375, AC1376)
2012-02-23
Operation
Set AS-i address of the safety monitor
449
14.15
Set AS-i address of the safety monitor
5987
The following method allows you to set the same AS-i address for the safety monitor in the device as
that already stored in the safety monitor using the safety parameter setting software "ASIMON".
This is why the AS-i master can now exchange data with the safety monitor via a special protocol.
More information on the protocol
device manual of the safety monitor.
WARNING
The protocol changes output states of the set slaves.
Danger for people and machine by uncontrolled machine states.
►
Set AS-i safety monitors in this menu only.
[MENU] > [Diagnostics] > Select safety master > [Enable Monitor]
MENU
0
USER
Step 1:
►
Press [Menu].
.
Quick Setup
PLC Setup
Slave Lists
OK
1
ESC
Step 2:
►
Press [ ] to scroll to [Diagnostics].
Slave Lists
Address Slave
Diagnostics
OK
1
ESC
Step 3:
►
Select [Diagnostics] with [OK].
.