Operation
Reset diagnostic states of safety devices
458
14.18
Reset diagnostic states of safety devices
5996
The following method can be used to delete the stored diagnostic states of the safety devices.
Info
Password level 1 required:
chapter Password setting (
→
page
.
[MENU] > [Diagnostics] > Select safety master > [Reset all] > [OK]
.
MENU
0
USER
Step 1:
►
Press [Menu].
.
Quick Setup
PLC Setup
Slave Lists
OK
1
ESC
Step 2:
►
Press [ ] to scroll to [Diagnostics].
.
Slave Lists
Address Slave
Diagnostics
OK
1
ESC
Step 3:
►
Select [Diagnostics] with [OK].