205
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Appendix
Fieldbus EtherNet/IP
>
Diagnosis - AS-i master 2: AS-i diagnosis
12730
AS-i master 2: AS-i diagnostics:
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
26
-
-
PF19
PF22.
5
EF
S0
PM
IME
-
-
-
DAE
PE
CEIP
CEAS CEMS
27
Voltage AS-i+ to AS-i- in mV
28
Voltage FE to AS-i- in mV
29
Symmetry in % (-100% ... +100%)
Legend:
Alarm
Description
IME
internal master error: Internal system error of an AS-i master
PM
projection mode: AS-i master was set to the projection mode.
S0
slave 0 detected: New slave 0 was detected.
EF
earth fault: Earth fault was detected
PF22.5
22.5V AS-i Power-Fail (classic AS-i Power) was detected.
PF19
19 AS-i Power-Fail (Power24) was detected.
CEMS
Configuration Error
– Missing Slave: AS-i configuration error, one or several slaves are projected, but not
available.
CEAS
Configuration Error
– Additional Slave: AS-i configuration error, one or several slaves are available, but
not projected.
CEIP
Configuration Error
– Invalid Profile: AS-i configuration error, the slave profiles of one or several slaves
differ from the projected slave profiles.
PE
periphery error: One or several AS-i slaves have a periphery error.
DAE
duplicate address error: One or several multiple-addressing faults occurred.
>
Diagnosis - AS-i master 2: list of missing slaves
12731
AS-i master 2: list of missing slaves:
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
30
15(A) 14(A) 13(A) 12(A) 11(A) 10(A)
9(A)
8(A)
7(A)
6(A)
5(A)
4(A)
3(A)
2(A)
1(A)
0
31
31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)
32
15B
14B
13B
12B
11B
10B
9B
8B
7B
6B
5B
4B
3B
2B
1B
n.a.
33
31B
30B
29B
28B
27B
26B
25B
24B
23B
22B
21B
20B
19B
18B
17B
16B
If at least 1 bit is set in this list, the bit for CEMS is also set.
(
→