222
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Appendix
Fieldbus EtherNet/IP
>
DS1 – System information
8753
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Article number
1
) (byte 0) = "A"
Article number
1
) (byte 1) = “C"
1
Article number
1
) (byte 2) = A
1
Article number
1
) (byte 3) = A
2
2
Article number
1
) (byte 4) = A
3
Article number
1
) (byte 5) = A
4
3
Device number
2
) (byte 1) = G
1
Device number
2
) (byte 0) = G
2
4
Serial number
3
) (byte 0, MSB)
Serial number
3
) (byte 1)
5
Serial number
3
) (byte 2)
Serial number
3
) (byte 3)
6
Serial number
3
) (byte 4)
Serial number
3
) (byte 5)
7
Serial number
3
) (byte 6)
Serial number
3
) (byte 7)
8
Serial number
3
) (byte 8)
Serial number
3
) (byte 9)
9
Serial number
3
) (byte 10)
Serial number
3
) (byte 11)
10
Software type
Software Version (Major Version)
11
Software Version (Minor Version)
Software Version (Build Version)
12
Operating hours
5
) Total (byte 3, high byte)
Operating hours
5
) Total (byte 2)
13
Operating hours
5
) Total (byte 1)
Operating hours
5
) Total (byte 0, low byte)
14
Operating hours
5
) Uptime (byte 3, high byte)
Operating hours
5
) Uptime (byte 2)
15
Operating hours
5
) Uptime (byte 1)
Operating hours
5
) Uptime (byte 0, low byte)
16
Operating hours
5
) PLC (byte 3, high byte)
Operating hours
5
) PLC (byte 2)
17
Operating hours
5
) PLC (byte 1)
Operating hours
5
) PLC (byte 0, low byte)
18
Operating hours
5
) display (byte 3, high byte)
Operating hours
5
) display (byte 2)
19
Operating hours
5
) display (byte 1)
Operating hours
5
) display (byte 0, low byte)
20
Device temperature
6
) (byte 0, high byte)
Device temperature
6
) (byte 1, low byte)
21
reserved
Number of AS-i masters
22
Language
7
) (1st letter)
Language
7
) (2nd letter)
23
Return to start screen (on/off)
Screen saver (on/off)
24
CODESYS PLC operating mode (activ/inactiv)
Output access
25
Device cycle in µs (high byte)
Device cycle in µs (low byte)
1
) Article number: "AC" + A
1
+ A
2
+ A
3
+ A
4
as character string, e.g. "AC1401" or "AC402S"
2
) Device number: G
1
+ G
2
as character string, e.g. "AB"
3
) Serial number: 12-digit character string
5
) Operating hours: in seconds, Unsigned Double word (32 bit)
6
) Device temperature: in 1/100 °C, signed Word (16 bit), e.g. 4232 = 42.32 °C
7)
Language: LANG_ID as ASCII code, e.g. "DE" = "D" + "E" = 0x44 + 0x45