257
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Appendix
Fieldbus EtherNet/IP
>
Command 262 (0x0106) – Set PLC operating mode
16674
Using this command, the operating mode of the device-internal PLC can be set.
>
Command request channel (fieldbus master >>> device)
16689
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
UID
2
command number
3
reserved
reserved
PLC
4 ... 120
The area is completely ignored.
It does not matter whether the data area exists or what data is contained.
Legend:
PLC
Operating mode of the
device-internal PLC
1 bit
0x00 = stop PLC application and switch off PLC
0x01 = switch on PLC and start PLC application (boot application)
>
Command response channel (device >>> fieldbus master)
16690
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
2
reflected command number
3
reserved
Command status
(
→ page
4
command error code
>
Possible command error codes
16691
Error Code
[hex]
Error
Meaning
0x00
no error
0x01
PF
PLC operating mode could not be set.
Error code only appears if command status = FAILED.