276
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Appendix
Fieldbus EtherNet/IP
>
Command 03 (0x0003) – Project the currrent AS-i network
8805
(= project all)
Requirement:
The addressed AS-i master must be in the projection mode.
Command 05 (0x0005) – Change the operating mode of the AS-i master
(
This command causes a reset of the fieldbus connection. The device must be rebooted!
>
Command request channel (fieldbus master >>> device)
11107
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
UID
2
command number
3 ... 120
The area is completely ignored.
It does not matter whether the data area exists or what data is contained.
Legende:
UID
user ID
1 word
0x0000…0xFFFF = 0…65535
The user ID ensures clear identification of the commmand response data
of the command request data sent before. The user can assign any user
ID in the command request. The AS-i master reflects the user ID from the
command request into the corresponding command response.
>
Command response channel (device >>> fieldbus master)
11086
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
reflected user ID
2
reflected command number
3
reserved
Command status
(
→ page
4
command error code
>
Possible command error codes
11109
Error Code
[hex]
Error
Meaning
0x00
no error
0x03
SD0
slave with address 0 connected
0x19
master is not in projection mode