58
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Menu
AS-i 1 / AS-i 2
>
Carry out a projection adaptation
8938
During projection adaptation, the AS-i master stores the configuration of all AS-i slaves currently found
on the AS-i network in its memory and assigns a valid AS-i address to each of them.
The projection adaptation can only be carried out in projection mode:
► [Projection mode] must be checked (→
Set the operating mode of the AS-i master
(
To launch the projection adaptation:
1 Select the menu page
►
>
or
>
2 Carry out a projection adaptation
►
Press [Start projection process] button.
>
The projection adaptation is carried out.
If successful:
>
All slaves on the AS-i master are projected.
If not successful:
>
The Online Support Center displays an error message.
►
Remove the error and repeat the process.
>
Set the monitoring functions of the AS-i master
11728
To set the monitoring functions of the selected AS-i master:
1 Select the menu page
►
>
or
>
2 Set the monitoring functions of the AS-i master
►
Set the following parameters as required:
Parameter
Meaning
Possible values
[Automatic addressing]
Behaviour if AS-i slave is
replaced
=
New AS-i slave obtains the next free address
=
The new AS-i slave obtains the same address
as the old AS-i slave if the following conditions
are met:
– The new AS-i slave has the address
0
.
– The old and the new AS-i slave have the
same slave profile.
[Earth fault detection]
Detection of earth faults
=
Do not detect earth faults in the AS-i system
=
Detect earth faults in the AS-i system
[Double address
detection]
Double address detection
=
Do not detect AS-i slaves with the same
address
=
Detect AS-i slaves with the same address
>
Selected values are applied.