Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Appendix
Fieldbus EtherNet/IP
>
Diagnosis - AS-i master 1: AS-i diagnosis
12658
AS-i master 1: AS-i diagnostics:
Offset
Word no.
bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
2
-
-
PF19
PF22.
5
EF
S0
PM
IME
-
-
-
DAE
PE
CEIP
CEAS CEMS
3
Voltage AS-i+ to AS-i- in mV
4
Voltage FE to AS-i- in mV
5
Symmetry in % (-100% ... +100%)
Legend:
Alarm
Description
IME
internal master error: Internal system error of an AS-i master
PM
projection mode: AS-i master was set to the projection mode.
S0
slave 0 detected: New slave 0 was detected.
EF
earth fault: Earth fault was detected
PF22.5
22.5V AS-i Power-Fail (classic AS-i Power) was detected.
PF19
19 AS-i Power-Fail (Power24) was detected.
CEMS
Configuration Error
– Missing Slave: AS-i configuration error, one or several slaves are projected, but not
available.
CEAS
Configuration Error
– Additional Slave: AS-i configuration error, one or several slaves are available, but
not projected.
CEIP
Configuration Error
– Invalid Profile: AS-i configuration error, the slave profiles of one or several slaves
differ from the projected slave profiles.
PE
periphery error: One or several AS-i slaves have a periphery error.
DAE
duplicate address error: One or several multiple-addressing faults occurred.