75
ifm
Device Manual SmartSPS AC14 with EtherNet/IP interface (AC1421, AC1422), Firmware 3.1.2
2015-11-30
Menu
System
>
5.4.3
System: Setup
7274
The [Setup] menu item provides access to the configuration options of the system.
>
Set the output access
9100
To set the control instance for the outputs of the AS-i slaves:
1 Select the menu page
►
>
►
Select [System settings] tab.
2 Configure the control instance for the outputs of the AS-i slaves
►
From the [Output access] list, select the required value:
Parameter
Meaning
Possible values
[Output access]
Control instance of the AS-i
slave outputs
Gateway
=
A higher-level PLC controls the outputs of
the AS-i slaves.
Manual
=
The operator controls the outputs of the
AS-i slaves via the graphical user interface.
PLC
=
The device-internal PLC controls the
outputs of the AS-i slaves.
3 Save the changes
►
Press [Accept selection] to save the changes.
>
The selected instance controls the outputs of the AS-i slaves.
If the value
PLC
is selected, the system will automatically enable the device-internal PLC
(
→
Enable/Disable the device-internal PLC
(