MK59xx

Cylinder sensor with IO-Link

16

The switch points SP1 and SP2 must have a minimum distance to the limits of the measuring
range (0 and 4000) in the size of the hysteresis. This restriction applies to each mode, so that it
is possible to switch between the switch point modes.

If the hysteresis is set to 0, the device adopts the [Auto] setting. This setting corresponds to a
hysteresis value of 100.

9.2 Teach functions

The three teach functions can be used to teach switch points for the switching signal channels SSC1.1
and SSC1.2 based on the current magnet position.

The application teach-in also allows automatic parameter setting of the stroke time monitoring

 (

Ò

Stroke time monitoring parameter setting 

/

 21)

.

9.2.1 Switch point teach

In case of the switch point teach [Teach SPx], the switch points are taught individually for the selected
switch channel SSC1.x on the basis of the current magnet position. The switch point mode can be
freely selected.

In [Single Point] mode, the current measured value plus the set hysteresis is adopted as switch point
SP1, so that the switch point has a reserve when the cylinder is fully in the end position:

SP1 = current measured value + hysteresis

In the [Window] mode and in the [Two Point] mode, the switch point SPx is set exactly to the current
measured value:

SP1 = current measured value at end position 1

SP2 = current measured value at end position 2

A switch point teach can also be carried out by means of manual configuration

 (

Ò

 Setting

switch points 

/

 15)

.

Parameter setting:

u

Install the device in the groove.

u

Select [Parameter] > [Output configuration] > [oux] and set the switching signal channel [SSC1.x].

u

Select [Parameter] > [SSC1.x].

Single point mode:

u

[SSC1.x Config. ]Select [Mode] and set the switch point mode: [Single Point].

u

Move the cylinder to the required end position 1.

ü

Check that the current measured value is within the limits of the measuring range.

u

Select [Parameter] > [Teach].

u

Select [TI Select] and set the switching signal channel [SSC1.x].

w

The following teach will be executed for the selected switching signal channel.

If [TI Select] = [all SSC] is selected, the teach is carried out for both switching signal channels
simultaneously.

u

Execute command: [Teach SP1].

w

[TI Result. State] shows the status of the teach process.

w

The switch point SP1 is set for the selected switching signal channel.

Window and Two Point Mode:

u

[SSC1.x Config. ]Select [Mode] and set the switch point mode: [Window] or [Two Point].

Summary of Contents for MK59 Series

Page 1: ...Operating instructions Cylinder sensor with IO Link MK59xx 11463922 00 12 2022 GB...

Page 2: ...5 9 1 Setting switch points 15 9 2 Teach functions 16 9 2 1 Switch point teach 16 9 2 2 Section Teach 17 9 2 3 Teach In Application 18 9 3 Switch point logic 19 9 4 Switching delay 19 9 5 Signal direc...

Page 3: ...cessories and further information using the QR code on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross r...

Page 4: ...architect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental co...

Page 5: ...sensor with IO Link MK59xx 5 3 Items supplied Cylinder sensor Cable clip Rubber placeholder The following are additionally required for installation hexagon socket 1 5 mm or slotted screwdriver not i...

Page 6: ...al aluminium brass or stainless steel Special adapters for mounting on the following cylinder profiles are available as accessories Clean line and tie rod cylinders Integrated profile cylinder Trapezo...

Page 7: ...omagnetic materials iron permanent magnets and magnetic fields in the vicinity of the device or the encoder magnet can influence and falsify the signal 5 2 Signal range The device provides a measured...

Page 8: ...between the following switch point modes according to the IO Link smart sensor profile Function Class Object Detection Deactivated Single Point Window Two Point Deactivated If the Deactivated mode is...

Page 9: ...d can be used to shut down a device or valve prematurely so that the cylinder moves more smoothly into the end stop Cylinder shortly before the end position e g at 80 of the end position LED 1 is on T...

Page 10: ...tion Thanks to accurate position detection process deviations can be monitored such as the drift of an operation as well as wear and soiling In this way quality monitoring can be carried out independe...

Page 11: ...scriptions of the device at documentation ifm com IO Link offers the following advantages Interference free transmission of all data and process values Parameter setting in the running process or pres...

Page 12: ...er towards the end position w LED2 goes on when the switch point SSC1 2 SP1 is reached When both LEDs are on this indicates the middle of the switching area 2 u Fix the device in this position using t...

Page 13: ...pply according to SELV PELV u Disconnect power u Connect the unit as follows L 1 BN 2 WH 4 BK 3 BU OUT1 IO Link OUT2 L 4 3 2 1 Fig 5 Wiring diagram colours to DIN EN 60947 5 2 BK black BN brown BU blu...

Page 14: ...of the switching signal channel If the switching signal channel is set to the switch point logic High active the LED goes on when the output is closed If the switching signal channel is set to the swi...

Page 15: ...evice to a free port of the IO Link master w The unit switches to IO Link mode u Change parameter settings in the software u Write parameter settings to the unit Notes on parameter setting Manual of t...

Page 16: ...der is fully in the end position SP1 current measured value hysteresis In the Window mode and in the Two Point mode the switch point SPx is set exactly to the current measured value SP1 current measur...

Page 17: ...x are taught using the current magnet position in an end position and the switch point mode is automatically set to Window The switch points SP1 and SP2 are calculated with the current measured value...

Page 18: ...least twice the value of hysteresis SSC1 1 and hysteresis SSC1 2 apart PDVmax PDVmin 2x SSC1 1 Config Hyst 2x SSC1 2 Config Hyst Parameter setting 1x 2x 1x 2x 3x PDV 0 4000 Min Max 3x Fig 7 Example al...

Page 19: ...switch point logic for the switching signal channel SSC1 x 9 4 Switching delay For both switching signal channels a separate delay time can be set for the output to switch and to be reset A switching...

Page 20: ...re a Teach In Application the assignment of the LEDs can also be changed Parameter setting u Select Parameter Signal Signal direction to set the signal direction 9 6 Output polarity of the switching o...

Page 21: ...hreshold value for the switching cycles counter SCT1 1 has been reached Overflow SCT1 2 Switching cycle monitoring 23 The threshold value for the switching cycles counter SCT1 2 has been reached NoDat...

Page 22: ...e setting range will be automatically corrected to the minimum or maximum value during application teach Manual parameter setting u Parameter setting of switching signal channels SSC1 1 and SSC1 2 Det...

Page 23: ...le threshold is reached The switching status remains active for the set hold time SSC EnhCrt_HoldTime SSC1 x Afterwards the switching output and the counter are reset The counter starts again at 0 SSC...

Page 24: ...rength Parameter Signal 9 8 3 1 Configuring magnetic field monitoring u Call up Parameters Output Configuration u Select oux and set the diagnostic function for output OUTx dOU diagnostic output u dFU...

Page 25: ...ion 1 SSC1 2 indicates that the cylinder is in end position 2 In this example the south pole of the magnet is oriented towards the cylinder rod therefore the signal falls when the cylinder is extended...

Page 26: ...ter set and write it to the device u Retract the cylinder to end position 1 u Select Parameter Teach Teach Single Value u Select TI Select and set SSC1 2 u Save the parameter set and write it to the d...

Page 27: ...ct SSC1 1 Config Logic and set High active u Save the parameter set and write it to the device u Select SSC1 2 Config Mode and set Window u Set the same switch points as for switching signal channel S...

Page 28: ...and write it to the device u Retract the cylinder completely u Select SSC1 2 Config Mode and set Window u Calculate and set the switch points for switching signal channel SSC1 2 SSC1 2 Param SP1 3000...

Page 29: ...nit This includes Product name Product family Manufacturer Manufacturer ID Device ID Serial number Hardware firmware revision Description In addition further freely definable tags with a maximum lengt...

Page 30: ...n After power on and the required parameter setting the device is in the operating mode It carries out its measurement and evaluation functions and generates output signals according to the set parame...

Page 31: ...switch point teach has been carried out When the cylinder returns to the end po sition the device will not switch With the switch point teach the switch point is shifted by the hysteresis to the teac...

Page 32: ...to repair the unit u In case of return shipment ensure that the unit is free from soiling especially from dangerous and toxic substances u For transport only use appropriate packaging to avoid damage...

Page 33: ...SSC1 1 Diagnostic output dFU1 3 Overflow SCT1 1 Output configuration ou2 2 SSC1 2 Diagnostic output dFU2 3 2 Overflow SCT1 2 SSC EnhCtr_AutoReload SSC1 x OFF SSC EnhCtr_HoldTime SSC1 x 10000 ms SSC En...

Reviews: