20
10.2.8 Configuration of OUT1
►
Select [OU2]�
►
Set the switching functions or analogue signals:
• [Hno] = hysteresis function / normally open
• [Hnc] = hysteresis function / normally closed
• [Fno] = window function / normally open
• [Fnc] = window function / normally closed
• [I] = current output analogue 4���20 mA
• [U] = voltage output analogue 0���10 V
►
Confirm with [MODE/ENTER]�
10.2.9 Setting of the switch point for hysteresis function OUT2
►
Select [Hno] or [Hnc] at [OU2]�
►
Confirm with [MODE/ENTER]�
►
Select [SP2] and set the switch point�
►
Confirm with [MODE/ENTER]�
10.2.10 Setting of the switch points for window function OUT2
►
Select [Fno] or [Fnc] at [OU2]�
►
Confirm with [MODE/ENTER]�
►
Select [nSP2] and set the switch point "near"�
►
Confirm with [MODE/ENTER]�
►
Select [FSP2] and set the switch point "far"�
►
Confirm with [MODE/ENTER]�
10.2.11 Scaling of the measuring range (analogue output)
►
Select [I] or [U] at [OU2]�
►
Confirm with [MODE/ENTER]�
►
Select [ASP] and set "Analogue start point"�
With [ASP] you define at which measured value the output signal is 4
mA / 0 V�
►
Confirm with [MODE/ENTER]�
►
Select [AEP] and set the "Analogue end point"�
With [AEP] you define at which measured value the output signal is
20 mA / 10 V� It can also be selected so that it is before [ASP]� This
implements a falling edge�
►
Confirm with [MODE/ENTER]�
Minimum distance between [ASP] and [AEP]:100 mm
When the minimum distance is not reached, the error message "SIZE" is
displayed�