12
8.2 Menu explanation
SP1/rP1
Maximum / minimum value for system pressure, at which output 1 changes
its switching status�
OU1
Output function for OUT1:
• Switching signal for the limit values: hysteresis function [H ��] or window
function [F ��], normally open [� no] or normally closed [� nc] each�
OU2
Output function for OUT2:
• Switching signal for the limit values: hysteresis function [H ��] or window
function [F ��], normally open [� no] or normally closed [� nc] each��
• Analogue signal for the current system pressure: 4���20 mA [I], 0���10 V [U]�
SP2/rP2
Maximum / minimum value for system pressure, at which output 2 changes
its switching status�
ASP
Analogue start point for the system pressure: measured value at which
4 mA / 0 V are output�
AEP
Analogue end point for the system pressure: measured value at which
20 mA / 10 V are output�
EF
Extended functions / Opening menu level 2�
HI
Maximum value memory for the system pressure�
LO
Minimum value memory for the system pressure�
COF
Zero point calibration�
CAr
Calibration reset�
dS1/dS2
Switch-on delay for OUT1/OUT2�
dr1/dr2
Reset delay for OUT1/OUT2�
P-n
Output polarity: pnp / npn
dAP
Damping for the switching outputs�
dAA
Damping for the analogue signal�
diS
Update rate and orientation of the display�
Uni
Standard unit of measurement for the system pressure�