20
8.6 Explanation of menu level 3
With setting SEL = OU
SEL
Status to be simulated:
• Output functions [OU]�
S�OU1*
Simulation values for OUT1, only active for 3-wire operation and if
[SEL] = [OU]�
• Output inactive [OPEN] or output active [CLOS]�
S�OU2
Simulation values for OUT2, only active if [SEL] = [OU]�
• For 3-wire operation and if OUT2 has been configured as switching output:
output inactive [OPEN] or active [CLOS]�
• If OUT2 is set as analogue output: analogue signal between 3�6 and
21.1 mA (depending on the set value → 9.6.2).
S�TIM
Time for the simulation process in minutes�
S�ON
Start of the simulation process�
During the simulation process the display alternately shows [SIM] and the
current operation indication (→ 9.6.4).
If the simulation process is aborted (briefly press [Mode/Enter] or [Set])
[S�OFF] is indicated for 2 s, then [SEL] is active again�
* menu item not active in 2-wire operation
With setting SEL = Proc
SEL
Status to be simulated:
• Process value [Proc]�
S�Pr
Simulation of a process value, only active if [SEL] = [Proc]�
• Any value between initial value of the measuring range and final value of
the measuring range�
S�TIM
Time for the simulation process in minutes�
S�ON
Start of the simulation process�
During the simulation process the display alternately shows [SIM] and the
current operation indication (→ 9.6.4).
If the simulation process is aborted (briefly press [Mode/Enter] or [Set])
[S�OFF] is indicated for 2 s, then [SEL] is active again�