26
9.4 User settings (optional)
9.4.1 Carry out zero point calibration
►
Select [COF] and set a value between -5 % and 5 % of the final value of
the measuring range� The internal measured value "0" is shifted by this
value�
Alternatively: automatic adjustment of the offset in the range 0 bar ± 5 %�
►
Make sure that no pressure is applied to the system�
►
Press [Mode/Enter] until [tCOF] appears�
►
Press and hold down [Set]�
> The current offset value (in %) flashes briefly�
> The current system pressure is displayed�
►
Release [Set]�
►
Briefly press [Mode/Enter] (= to confirm the new offset value)�
9.4.2 Set output status in fault condition
►
Select [FOU1] and set the value:
-[On] = output 1 switches ON in case of a fault�
-[OFF] = output 1 switches OFF in case of a fault�
-[OU] = output 1 switches irrespective of a fault as defined with the
parameters SP1, rP1 and OU1�
►
Select [FOU2] and set the value:
-[On] = output 2 switches ON in case of a fault, the analogue signal
goes to the upper final value�
-[OFF] = output 2 switches OFF in case of a fault, the analogue signal
goes to the lower final value�
-[OU] = output 2 switches irrespective of the fault as defined with the
parameters SP2, rP2, OU2� The analogue signal corresponds to the
measured value�
Fault indications → 10.3
9.4.3 Set delay time for the switching outputs
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2�
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2�
►
Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0�1 and 50 s
(at 0�0 the delay time is not active)�
9.4.4 Set output logic for the switching outputs
►
Select [P-n] and set [PnP] or [nPn]�