The unit must only be connected by an electrician.
The national and international regulations for the installation of elec-
trical equipment must be observed.
Voltage supply to EN50178, SELV, PELV
Use a suitable power supply (according to the voltage range of the
connected EPS sensor).
Connect PP2000, sensor and plant via the plug and socket
connections only!
Do not disconnect these connections while live.
Disconnect power before connecting the unit.
The connection of the outputs during operation depends on the sen-
sor (
→
operating instructions of the appropriate sensor).
The sensor output signal OU1 is transferred to the PP2000 via the EPS
protocol. To avoid malfunction due to interference voltage a shielded
cable is recommended in case of a larger distance between sensor and
PP2000.
page 17
ENGLISH
There are two
options
Use of PP2000 prior to
installation of the sensor
Mobile use of the
PP2000 after installation
of the sensor
Hard-wiring of the
PP2000
Installation
Electrical connection
Core colours of ifm
sockets:
1 = BN (brown),
2 = WH (white),
3 = BU (blue),
4 = BK (black).
Set
Mode/Enter
L-
L+
OU1
OU2
3
1
2
4
4
2
1
3
Pin 1 / BN
Pin 2 / WH
Pin 4 / BK
Pin 3 / BU
EPS sensor
A
A
B
1
2
Mount the unit with a mounting
clamp (A)
(to be ordered separately,
order no. E10077).
Mount the unit in a mounting base
with clearance hole (A). Diameter of
the hole 18.5mm to 20mm.
- Remove the threaded sleeve (B),
- fit the unit,
- screw on the sleeve and tighten it.