706414/00 

Page 11 of 14 

© ifm efector gmbh 

 

 

4  Hex parameter setting for multiturn class 2: 

 
 

Hex parameter setting means that the device-specific parameters are written in HEX coding. 
These settings 

do not have to be 

made if already set in the device-specific parameters. 

 
 
 

 

 
 
 
Octet 9 
 Octet 

10 

  Octet 

11 

   Octet 

12 

 

 

 

 

Octet 13 

 

 

 

 

 

Octet 14 

 

 

 

 

 

 

Octet 15 

 

 

 

 

 

 

 

Octet 16 

 

 

 

 

 

 

 

 

Octet 17 

 
,02 (HEX - CODE) 
 
0000 

0010 (BINARY CODE) 

 
Meaning (read from right to left): 
 
Octet 9 bit 0 => 0 = clockwise // 1 counterclockwise 
Octet 9 bit 1 => 0 = class 2 disable // 1class 2 enable 
Octet 9 bit 2 => 0 = "optional" set-up diagnosis No // 1 Yes 
 
 

 
 
 
 
 
 
 
 
 
 

Summary of Contents for RM30 Series

Page 1: ...706414 00 Page 1 of 14 ifm efector gmbh RM30xx Profibus Brief instructions efector400...

Page 2: ...examples 9 3 2 Setting examples with high and low word 10 4 Hex parameter setting for multiturn class 2 11 5 List of variables reset and preset 12 5 1 Display variables 12 5 2 Reset 13 5 3 Preset 13 6...

Page 3: ...GSD file Example RM3006 gsd DPV0 2 Hardware catalogue Install GSD first unzip the ZIP file 3 Additional Field Devices Encoder select ifm Encoder see chapter 2 4 Drag the encoder into the project and a...

Page 4: ...tor gmbh DP V2 isochronous data exchange lateral communication between the slaves and time synchronisation 1 2 Hardware 1 2 1 Overview 1 voltage supply Ub GND 2 bus IN 3 bus OUT 4 addressing 5 termina...

Page 5: ...706414 00 Page 5 of 14 ifm efector gmbh...

Page 6: ...rn This setting enables the setting of the direction of rotation diagnostic function and scaling of the measuring units at 8192 units Class2 Multiturn standard This setting enables the setting of the...

Page 7: ...HW Config DP Slave Properties Assigning Parameters Setting options Code sequence Counterclockwise clockwise Class 2 functionality Enable disable Scaling function control Enable scaling disable scaling...

Page 8: ...xample 8192 x 2 revolutions total 16384 1 2 8192 8193 16383 16384 1 2 Input of the figures Maximum units 8192 units x 4096 revolutions total measuring range 33 554 432 The revolutions must never be mo...

Page 9: ...g units per revolution The total measuring range must be calculated Example 2000 pulses x 9 revolutions 18 000 Standard Scaling function disabled Resolution per revolution 8192 x revolutions 4096 tota...

Page 10: ...g range 33 554 432 in hex 0200 0000 hex high word 0200 hex in decimal 512 low word 0000 hex in decimal 0 200 units x 24 revolutions enable scaling 200 units x 24 revolutions total measuring range 4800...

Page 11: ...These settings do not have to be made if already set in the device specific parameters Octet 9 Octet 10 Octet 11 Octet 12 Octet 13 Octet 14 Octet 15 Octet 16 Octet 17 02 HEX CODE 0000 0010 BINARY CODE...

Page 12: ...ay variables Simatic Manager CPU 315 2 select TAB PLC Monitor control variable Display measured value Operand ED 100 for set input address 100 103 display format DEC and monitor variables Attention Wh...

Page 13: ...8000 0000 OPERAND DISPLAY FORMAT STATUS VALUE CONTROL VALUE ED 100 Dec L 0 AD 100 Hex DW 8000 0000 8000 0000 5 3 Preset Operand AD 100 for set E address 100 103 display format HEX enter 8 at the first...

Page 14: ...it 1000 0000 0000 0000 0000 0000 0000 0000 BINARY CODING Bit numbers 31 2827 24 23 20 19 16 15 12 11 8 7 4 3 0 Example decimal to binary 8 bits 1 byte octet 16bits 2 bytes word 32bits 4 bytes double w...