SDGx50
Flow meter compressed air
26
11 Parameter setting
The parameters can be set via the IO-Link interface or via the keys on the unit.
CAUTION
If the medium temperature is above 50 °C (122 °F), parts of the housing can increase in
temperature to over 65 °C (149 °F).
w
Risk of burns
u
Do not touch the device with your hands.
u
Use another object (e.g. a ballpoint pen) to carry out settings on the unit.
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u
Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
11.1 Parameter setting in general
Intention
Action
Change from the process value display to the main menu
[●]
Change to the submenu
Use [▼] to navigate to the sub-
menu (e.g. EF), then [●]
Select the requested parameter
[▲] or [▼]
Change to the setting mode
[●]
Modification of the parameter value
[▲] or [▼] > 1 s
Apply the set parameter
[●]
Exit parameter setting without saving
[▲] and [▼]
Return to the next higher menu level
(repeat several times to reach process value display)
[▲] and [▼]
Return to the process value display
> 30 seconds (timeout)
11.2 Presets
Before setting the parameters, first check the following default settings and change them if
necessary:
- [SEL1]: Process value for OUT1
- [SEL2]: Process value for OUT2
- [uni.F]: Standard unit of measurement for flow
- [uni.T]: Standard unit of measurement for temperature
- [uni.P]: Standard unit of measurement for pressure
11.2.1 Process value for OUTx
u
Select the OUTx menu.
u
Select [SELx] and set the process value for output x:
•
FLOW: Flow