Connection Possabilities
The 750 Series Module PCB Operates as an Interface ‘Hub’ on the Addressable 2-Wire Highway.
The Diagram Below Shows a Typical Set of Connection Possabilities
5
4/7
3/6
8/9
2
Option
1
2
3
4
5
6
7
8
9
Type
Input
Input
Input
Input
Output
Output
Output
Input
Input
Device
Gas DetectorPellistor
Toxic Gas Detector
TOC-10
4-20mA
Relay & OP1
Solid State Output
Solid State Output
E-Stop
Key Switch
Device Address
1
2
3
4
102
103
104
5
6
Device Address Table
Note that one 2-Wire addressable highway running S protocol can support up to 32 modules.
Each module can have up to 8 connected devices. IGD Configuration software is used to configure the
module PCB to switch devices on and off and set addresses (see Tocsin 650/750 Manual). If the
connected devices have already been configured then the base address can be set from which all other
module addresses will sequentially follow. This is described later in this manual. Device addresses
indicated in the table are typical but can be individually set.
I/O Port 1
Either Input
or Output
I/O Port 2
Either Input
or Output
1