REFRIGERATION LTD 

 

10 

www.igloorefrigeration.com

 | 

Pastry Display Cases

 

 

/C1 

probe 1 offset 

0.0 

°C 

-50.0 

50.0 

/C2 

probe 2 offset 

0.0 

°C 

-50.0 

50.0 

/C3 

probe 3 offset 

0.0 

°C 

-50.0 

50.0 

rd 

control differential 

3.0 

°C 

19.0 

r1 

minimum set point value 

0.0 

°C 

-50.0 

r2 

r2 

maximum set point value 

15.0 

°C 

r1 

99 

r3 

select direct/reverse operation 

r4 

night-time set point delta 

3.0 

°C 

-50 

50 

c0 

compressor and fan start delay on power-up 

min 

100 

c1 

minimum time between consecutive compressor starts 

min 

100 

c2 

minimum compressor off time 

min 

100 

c3 

minimum compressor on time 

min 

100 

c4 

compressor on time with duty setting 

50 

min 

100 

cc 

continuous cycle duration 

15 

c6 

temperature alarm bypass after continuous cycle 

15 

d0 

type of defrost 

dI 

interval between defrosts 

199 

dt 

end defrost temperature set point 

12.0 

°C 

-50 

130 

dP 

maximum defrost duration 

30 

min 

199 

d4 

defrost when switching the instrument on 

d5 

defrost delay on power-up or when enabled by digital input 

min 

199 

d6 

freeze control temperature display during defrost 

dd 

dripping time 

min 

15 

d8 

alarm bypass time after defrost 

15 

d9 

defrost priority over compressor  protectors 

d/ 

defrost probe reading (2) 

°C 

dC 

time base 

A0 

alarm and fan temperature differential 

2.0 

°C 

-20 

+20 

AL 

absolute/relative temperature for low temperature alarm 

0.0 

°C 

-50 

+99 

AH 

absolute/relative temperature for high temperature alarm 

0.0 

°C 

-50 

+99 

Ad 

temperature alarm delay 

min 

199 

A4 

3rd input configuration 

11 

A7 

digital input alarm delay 

min 

199 

A8 

enable alarm “Ed” (end  defrost  by timeout) 

AC 

set point dirty condenser alarm 

60 

°C 

-50 

250 

AE 

dirty condenser alarm differential temperature 

3.0 

°C 

0.1 

20 

Acd 

dirty condenser alarm delay 

min 

250 

F0 

enable evaporator fan control 

F1 

evaporator fan control set point 

5.0 

°C 

-50 

130 

F2 

stop evaporator fan if compressor off 

F3 

evaporator fan status during defrost 

Fd 

post-dripping time 

2.0 

min 

15 

H0 

serial address 

207 

H1 

AUX output configuration 

H2 

enable keypad 

H4 

disable buzzer 

 

H5 

ID code (read-only) 

+199 

EZY 

restore the Default settings 

 

Summary of Contents for C3URHP

Page 1: ...Pastry Display Cases Models C3URP series C3URLP C3URHP C3URP Instruction Manual Tel 416 663 3051 Fax 416 663 5793 Toll Free 1 888 408 8819 124 Norfinch Dr Toronto ON M3N 1X1 REFRIGERATION LTD...

Page 2: ...ure regulation 7 5 MAINTENANCE 11 5 1 Cleaning and maintenance 11 6 SERVICE 12 6 1 Faults identification and repair 12 6 2 Service 14 List of Figures Figure 1 C3URP 2 Shelves 4 Figure 2 Placing the ho...

Page 3: ...ption of the unit C3URP series display cases have a dynamic cooling system All units are equipped with automatic condensate evaporation and automatic defrosting The electronic thermostat cooperates mo...

Page 4: ...ss 8 Shelf hook for glass shelf height angle adjustable 9 Serial plate 10 Control panel thermostat switches 11 Condensate container 12 Condenser cover DO NOT BLOCK air louver 13 Leveling legs 2 3 Tech...

Page 5: ...GLOO will not warranty any equipment that is connected to an extension cord or adapter plug The equipment may be turned on after confirmation of the fire protection efficiency with results of measures...

Page 6: ...e on metal elements should be removed only with extraction naphtha not applicable to items made of plastic Do not use other organic solvents When cleaning the unit do not use water jet The unit should...

Page 7: ...ensure proper conditions for the stored products do not load the shelves completely Ensure even load of shelves and not to exceed the maximum load The first filling of shelves should be performed afte...

Page 8: ...inside the equipment is displayed decimal places displayed after the comma Diode 6 On Off Switch Pressing this button alone for more than 3 sec switch On Off Pressing with other buttons pressed togeth...

Page 9: ...ccess to the latter is protected by password default 22 to prevent accidental or unauthorized modifications Accessing the type F parameters Press the SET button for more than 3 s if there are active a...

Page 10: ...n enabled by digital input 0 min 0 199 d6 freeze control temperature display during defrost 1 0 1 dd dripping time 2 min 0 15 d8 alarm bypass time after defrost 2 h 0 15 d9 defrost priority over compr...

Page 11: ...prevent moisture damage Door gaskets shelves and supports should be cleaned on a regular basis Fan blades and guards should be cleaned with a soft cloth 5 1 Cleaning and maintenance All maintenance se...

Page 12: ...be held responsible for any condenser damages in the case of non observance of condenser cleaning instructions Elements of equipment can corrode as result of improper use and maintenance To prevent d...

Page 13: ...ure sensor inside the chamber call authorized service L0 low temperature alarm lower than temperature range set within the equipment call authorized service HI high temperature alarm call authorized s...

Page 14: ...frigeration service Telephone number 416 663 3051 or toll free 1 888 408 8819 E mail service igloo400 com If after checking points described in chapter 6 1 Faults identification and repair and the equ...