background image

 

REFRIGERATION LTD 

 

Pastry Display Cases

 

| www.igloorefrigeration.com

 

 

4.1. Temperature regulation 

 

The thermostat is to obtain the set temperature within the equipment and maintain it within the determined 
temperature ranges. The manufacturer enters all settings of temperature regulators required for normal 
functioning of the equipment. Before primary actuation the user should control and possibly set the required 
temperature inside the equipment on the control panel. 

 

Digital display – displays the current temperature inside the equipment. 

It is forbidden to interfere with systemic parameters of the thermostat, as this can 
lead to serious consequences, including the damage of the cooling unit! 

 

 

 

 

 

 

 

 
WHAT DO DIODES ON CONTROL PANEL SIGNIFY 
Diode 1 - Compressor:
  This symbol is visible when the compressor is working.  It blinks when compressor actuation 

is delayed by security procedure. It blinks in the following cycle: two blinks – pause, when the constant 
working mode is activated. 

Diode 2 - Ventilator: This symbol is visible when evaporator ventilators are turned on. It blinks when the actuation 

of the ventilators is delayed by external disengagement or when another procedure is in progress. 

Diode 3 - Defrosting: This symbol is visible when the defrosting function is activated. It blinks when the actuation is 

delayed by external disengagement or when another procedure is in progress. 

Diode 4 - Alarm: This symbol is visible when the alarm is activated. 
Diode 5 - Current temperature: inside the equipment is displayed (decimal places displayed after the comma). 
Diode 6 – On/Off Switch: Pressing this button alone: for more than 3 sec. switch On/Off, Pressing with other 
buttons:
 pressed together with 8 activities/deactivates the continuous cycle. 
Diode 7 – Set/ Mute: Pressing this button alone: 1 sec. displays /sets the set point, more than 3 sec. accesses the 
parameter setting menu (enter password 22), mutes the audible alarm (buzzer), Start Up: hold the set/mute button 
for 1 sec. RESET current EY set / Pressed together (7 and 8) activate parameter reset procedure. 
Diode 8 – Defrost: Pressing this button alone: more than 3 sec. activates/deactivates the defrost. Pressing with 
other buttons:
 pressed together with 6 activates/deactivates the continuous cycle, Start Up: hold for 1 sec. displays 
firmware version. 
 

Figure 6 “Carel” thermostat control panel 

 

QuickFinder for CAREL 

 

Summary of Contents for CURHP2

Page 1: ...Pastry Display Cases Models CURP series CURLP CURHP CURP Instruction Manual Tel 416 663 3051 Fax 416 663 5793 Toll Free 1 888 408 8819 124 Norfinch Dr Toronto ON M3N 1X1 REFRIGERATION LTD...

Page 2: ...n 9 5 MAINTENANCE 12 5 1 Cleaning and maintenance 12 6 SERVICE 14 6 1 Faults identification and repair 14 6 2 Service 15 List of Figures Figure 1 CURP 4 Figure 2 placing the hooks in the frame 6 Figur...

Page 3: ...ption of the unit CURP series display cases have a dynamic cooling system All units are equipped with automatic condensate evaporation and automatic defrosting The electronic thermostat cooperates mod...

Page 4: ...egs 11 Serial plate 12 Control panel thermostat switches 2 3 Technical data Table 1 Technical data Model Voltage V Hz Ph Rated Current A Max shelf load lbs kg Weight lbs kg CURP2 115 60 1 8 max fuse 1...

Page 5: ...e protection efficiency with results of measures performed according to binding regulations 3 2 Unit Location Remove cardboard angles and protective foil Install the unit on a strong and leveled surfa...

Page 6: ...turning it on The unit should be cleaned with warm water not exceeding 40 C with a neutral detergent For washing and cleaning the equipment it is prohibited to use products containing chlorine and sod...

Page 7: ...ck and place it in the suitable position and at the suitable angle 7 Acorn nut of the screw 8 Silicon pad 9 Plasticizer pad 10 Screw 11 Inner frame 12 Display glass shelves of the frame 13 Bumper pads...

Page 8: ...quipment and shall ensure proper water condensate outflow during defrosting After transporting the equipment wait about 2 hours before starting up the unit To ensure proper conditions for the stored p...

Page 9: ...when the actuation of the ventilators is delayed by external disengagement or when another procedure is in progress Diode 3 Defrosting This symbol is visible when the defrosting function is activated...

Page 10: ...ter error manual Ed not active ON defrost ended by timeout On first defrost ended correctly CHt active ON dirty condenser alarm manual MODIFYING THE PARAMETERS Parameter navigation The operating param...

Page 11: ...st temperature set point 12 0 C 50 130 dP maximum defrost duration 30 min 1 199 d4 defrost when switching the instrument on 0 0 1 d5 defrost delay on power up or when enabled by digital input 0 min 0...

Page 12: ...with warm water and mild soap Make sure to cover the fan motor to prevent moisture damage Dore gaskets shelves and supports should be cleaned on a regular basis Fan blades and guards should be cleaned...

Page 13: ...d to use vacuum cleaner or compressed nitrogen to suck blow the dirt from between lamellas The seller shall not be held responsible for any condenser damages in the case of non observance of condenser...

Page 14: ...ty the condensate container The equipment does not reach the proper temperature the light is on Make sure that The main switch is on Temperature setting on the thermostat is properly set Thermostat wo...

Page 15: ...cuit This phenomenon constitutes a technical feature of cooling devices and does not signify equipment failure Steam precipitation on glasses is normal in the event of high relative air humidity excee...

Reviews: