16
ACC-SVN190B-EN
discharge pressure at the selected setpoint anytime the
compressor is operating.
Set Pressure Setpoint
The pressure setpoint should be adjusted to 250 psig
initially. When the ambient temperature is above 50°F
(10°C), the outdoor fan motor will be energized
continuously. When the ambient temperature is below
50°F, the pressure sensor reading is used to switch the
motor on or off. When the pressure is 15psi below the
set pressure the motor will be turned off. When the
pressure is 15psi above the set pressure, the motor will
be turned on.
After completion of installation and pressure setting
adjustment), reinstall the compressor and control box
access panels and secure with screws that were
removed.
Reconnect all power to the unit. Refer to
troubleshooting guide, if needed.
Figure 18.
Supplemental wiring diagram
DEV DES
DESCRIPTION
LAT1
AMBIENT TEMPERATURE 1
LAT2
AMBIENT TEMPERATURE 2
LOAM 1
LOW AMBIENT MODULE 1
LOAM 2
LOW AMBIENT MODULE 2
OFC1
OUTDOOR FAN CONTACTOR 1
OFC2
OUTDOOR FAN CONTACTOR 2
XDCR1
PRESSURE TRANSDUCER #1
XDCR2
PRESSURE TRANSDUCER #2
W
HITE
WHITE
RED
RED
BLACK
BLAC
K
BRO
WN
B
ROWN
BRO
WN
BROW
N
YELLOW
YELLOW
BROWN
BROWN
ORANGE
O
R
ANGE
BR
OWN
BROWN
O
R
ANGE
ORANGE
YELLOW
YELLOW
WHITE
WHITE
RED
RED
BLAC
K
BLACK
O
R
ANGE
ORANGE
B
LACK
RED
B
L
A
CK
ORAN
GE
BLU
E
BROWN
B
ROWN
BROWN
B
ROWN
W
HITE
WH
IT
E
R
ED
RED
BLACK
B
LACK
YELLOW
YELLOW
BROWN
BROWN
ORANGE
OR
ANGE
BROWN
BROWN
ORA
NG
E
ORANGE
YELLOW
YELLOW
RED
R
ED
BLACK, BLACK
BLACK
ORANGE
ORA
NGE
BLACK
RED
RED
BLAC
K
BLACK
GREEN
USE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
OTHER TYPES OF CONDUCTORS.
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
EQUIPMENT.
CAUTION
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.
SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.
N'UTILISER QUE DES CONDUCTEURS EN CUIVRE!
LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES
POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS.
L'UTILISATION DE TOUT AUTRE CONDUCTEUR PEUT
ENDOMMAGER L'ÉQUIPEMENT.
PRECAUCIÓN
ATTENTION
LOW AMBIENT KIT FOR 2ND CIRCUIT
12133356-B
TO
OUTDOOR
FAN MOTOR
1 HARNESS
TO
OUTDOOR
FAN MOTOR
2 HARNESS
FACTORY SETTINGS:
CUT OUT SPEED - MIN
HARD START - MIN
SETPOINT - 250 PSIG
HEAT PUMP
ONLY
HEAT PUMP
ONLY
FACTORY
WIRES
FACTORY
WIRES
CONNECTIONS FOR
DUAL TRANSDUCERS
ON SINGLE MODULE
NOTES:
JUMPER DEFAULT POSITION IS ON N.O. FOR COOLING
ONLY UNITS, MOVE JUMPER TO N.C. POSITION FOR
HEAT PUMP UNITS
REMOVE BLACK FACTORY WIRE FROM SOV1, AND
BLUE FACTORY WIRE FROM SOV2. CONNECT THE
ORANGE WIRE/S FROM THE REV VALVE TERMINAL/S
TO SOV1 AND SOV2. CONNECT THE BLACK FACTORY
WIRE TO THE BLACK SUPPLIED WIRE IN LOAM1, AND THE
BLUE FACTORY WIRE TO THE BLACK SUPPLIED WIRE IN
LOAM2.
WHEN LOW AMBIENT KIT IS INSTALLED IN A SEPARATE
ENCLOSURE THEN TERMINATE THE GREEN WIRE IN THE
ENCLOSURE AND THE MAIN CONTROL BOX
CONNECTIONS FOR DUAL CIRCUIT ON ONE
MODULE WITH SINGLE FAN ONLY.
LAT1
L3
T3
L2
T2
L1
T1
OFC1
OUT
GND
IN
XDCR1
L
A
T2
L3
T3
L2
T2
L1
T1
OFC2
OUT
G
N
D
IN
XDC
R2
SOV1
S
O
V2
3
3
1
UC-P5
1
2
LOAM 1
T AMBIENT
C
Y1
Y2
REV
V
ALVE
P1 & P2 BLK
P1 & P2 RED
P1 B.W.G.
P
2
B.W
.G
.
LINE 1
L
OA
D 1
LINE 2
L
OA
D 2
LINE 3
L
OA
D 3
N.O.
HEAT
PUMP
N.C.
LOAM 2
T AMBIEN
T
C
Y1
Y2
REV
VALVE
P1 & P
2
B
L
K
P1 & P
2
RE
D
P1 B.W.
G
.
P2 B.W.
G
.
L
INE 1
LOAD
1
LIN
E 2
LOAD
2
LIN
E 3
LOAD
3
N.O.
HEAT
PUMP
N.C.
OUT
GND
IN
XDC
R2
1
1
2
2
2
4
4