M A I N O P E R A T I O N M O D E / M E N U
10
MRBP.424321.001G2 Version 1.0 15/06/2020
- data archiving on SD card mode. Data is recorded correctly.
By using buttons
and
channel is changed.
To review measured channel current information, it is necessary to push the button
.
01:SN09501668
GAS: C
3
H
8
VALUE, %LFL: 0.0
BLANKING ZONE: 0.0
THRESHOLD 1: 10.0
THRESHOLD 2: 20.0
MAX.VALUE: 100.0
MIN.VALUE: 0.0
THRESHOLD 1 HYSTERESIS: 0.0
THRESHOLD 2 HYSTERESIS: 0.0
THRESHOLD 1 RESET: AUTO
THRESHOLD 2 RESET: AUTO
CL CONNECTION: PASS.2wires
CURRENT, mA: 4,000
In the top left corner is the channel number and sensor item tag; hereunder is the present
channel information.
To return to
the «
main operation mode
»
press button
or
.
2.2
MENU
To change control unit or channels settings,
it is necessary to enter the device’s
«
MENU
»,
that requires pressing the button
in the «
main operation mode
»
.
MENU
CONTINGENCIES
CHANNELS REBOOT
SETTINGS
CHANNELS SETTINGS
ARCHIVING SETTINGS
DEVICE INFO
For menu navigation use buttons
and
.
Necessary section selection
–
.
Quit the menu -
.
Operation modes, signaling and relay actuations are described in the Appendix D.