Initial operation
Operating Instructions of the dryve D3 V0.0
14/15
4.5.6
Speed
The speed can be adjusted continuously from 0% to 100% of the motor speed via the potentiometer P2. At 50% of the achieva-
ble speed, a lock is available for more precise setting.
The maximum achievable speed depends on the connected motor, a possibly existing gearbox and the connected linear or ro-
tary axis as well as the load to be moved.
4.5.7
Force setting
The maximum force of the drive, i.e. the maximum current output, should always be set correctly to suit the respective mechani-
cal structure. This also applies to the use in limit switch operation.
To determine and test the ideal setting for the limitation, select the operating mode
Tip mode
and the maximum.
Acceleration
.
Setting the optimal force limit:
1.
Turn the potentiometer for force limit P1 and the setpoint speed P2 clockwise to the end stop.
2.
Move the connected motor incl. load in a free direction.
3.
Reduction of the permissible force by a counterclockwise rotation of the potentiometer P1
4.
Restart the drive. The current limit LED 5 (yellow) becomes active and after approx. 3 - 5 seconds the dryve D3 exe-
cutes an overcurrent switch-off. This is manifested by a motor stop and a glowing of the LED 6 (red).
5.
Increase the force limitation in small steps by turning the potentiometer P1 clockwise
6.
Renewed drive of the motor
7.
Complete the settings
a.
The LED 5 (yellow) goes out after a maximum of 1 second -> correct adjustment of the force limitation
b.
The LED 5 (yellow) remains active for more than 1 second and possibly a motor stop is executed -> re-
newed increase in the force limit