Initial Operation 

D7_EN 

– V1.2 

11/14 

4.1.3 

Micro-Stepping 

If the motor controller is used in 

Pulse Mode

 (p.12), the desired micro step mode must be preselected by the combination of 

switch SW4 to SW6 and SW 8. 
By preselecting the micro steps per motor revolution, the precision, the resulting vibrations, and the noise of the motor can be 
directly influenced. 
The higher the micro steps, the better the precision and at the same time vibrations and noise are reduced to a minimum. 
 

Micro Step 

Step mode 

SW4 

SW5 

SW6 

SW8 

200 

1/1 Full Step 

ON 

ON 

ON 

ON 

400 

1/2 Step 

OFF 

ON 

ON 

ON 

800 

1/4 Step 

ON 

OFF 

ON 

ON 

1600 

1/8 Step 

OFF 

OFF 

ON 

ON 

3200 

1/16 Step 

ON 

ON 

OFF 

ON 

6400 

1/32 Step 

OFF 

ON 

OFF 

ON 

12800 

1/64 Step 

ON 

OFF 

OFF 

ON 

25600 

1/128 Step 

OFF 

OFF 

OFF 

ON 

 

 

Note 

If the 

Pulse Mode

 (p.12) is used, the selection of the executed micro steps per motor revolution in the master controller and 

in the motor controller must be the identical. 

If, for example, 200 micro steps per motor revolution are set in the motor controller, but 400 micro steps per motor revolution 
are set in the master controller, and the master controller issues the movement command for one motor revolution, the motor 
will execute 2 revolutions. 

The reason for this is that instead of the 200 pulses expected by the motor controller for one motor revolution, 400 pulses 
were now emitted by the master controller and these were converted into 2 motor revolutions. 

4.1.4 

Selection Constant Speed 

If the motor controller is use

Jog Mode

 (p.13), the desired speed must be preselected by the combination of switches SW4 to 

SW6 and SW8. 
Acceleration and deceleration are set to a fixed time value of 250 ms. 
The Micro Stepping is set to 25600 (1/128 Step). 
 

RPM 

SW4 

SW5 

SW6 

SW8 

50 

ON 

ON 

ON 

OFF 

100 

OFF 

ON 

ON 

OFF 

150 

ON 

OFF 

ON 

OFF 

200 

OFF 

OFF 

ON 

OFF 

250 

ON 

ON 

OFF 

OFF 

300 

OFF 

ON 

OFF 

OFF 

400 

ON 

OFF 

OFF 

OFF 

500 

OFF 

OFF 

OFF 

OFF 

 

4.1.5 

Drive Mode 

The desired operating mode is set via switch SW8. 
 

Drive Mode 

SW8 

Pulse Mode 

– Step/Direction 

ON 

Jog Mode 

– Constant Speed 

OFF 

 

Summary of Contents for motion Plastics dryve D7

Page 1: ...D7_EN V1 2 1 14 igus motion Plastics dryve D7 Step Direction Stepper Motor Control System Manual V 1 2 Website MotorShop http www igus eu motorshop Videos Tutorials www igus eu dryve tutorial...

Page 2: ...6 2 1 4 Environmental conditions 6 3 Installation 7 3 1 Mechanical Installation 7 3 2 Electrical Installation 7 3 2 1 Pin Assignment 8 3 2 2 Connection Scheme Signal In Output 8 3 3 Integration into...

Page 3: ...onal injury or damage to property resulting from misuse or unauthorised technical modification of the motor controller igus reserves the right to make changes and improvements to the product or the te...

Page 4: ...t or property damage NOTE Safety instructions marked with NOTE indicate a potential hazardous situation Disregard of the notice may possibly result in property damage 1 5 Electromagnetic Compatibility...

Page 5: ...of various additional switches and sensors Simple control With the JOG mode a pre selected speed can be started by simply applying a signal The rotational direction can be changed by connecting a seco...

Page 6: ...t frequency 2 Hz up to 1 MHz Step input signal width Min 250 ns Direction input signal width Min 50 s Dissipation Loss Max 144 W Digital Inputs Outputs Galvanically Separated by Optocoupler Boot up ti...

Page 7: ...tion The dryve D3 motor controller is constructed for use with direct currents Every voltage mentioned in this manual can be regarded as direct current WARNING Risk of injury Make sure that an emergen...

Page 8: ...EP Motion input ground 0 V DIR Motion input 5 V up to 24 V DIR Motion input ground 0 V EN Enable signal 5 V up to 24 V EN Enable signal ground 0 V NOTE If different power supplies are used for the sup...

Page 9: ...ld remain energised in a fault condition Switching off the control signals at STEP and DIR and delayed switching off of the load supply voltage Generation of a braking torque by emitting a holding cur...

Page 10: ...mmand is present the motor current set via switches SW1 to SW3 is reduced to 50 SW7 ON or 90 SW7 OFF at standstill The auto tuning function allows the motor controller to be optimally adapted to the c...

Page 11: ...be the identical If for example 200 micro steps per motor revolution are set in the motor controller but 400 micro steps per motor revolution are set in the master controller and the master controller...

Page 12: ...ode a 5 V to 24 V signal must be permanently applied to the EN input If a square wave signal is applied to the STEP input a clockwise motor step is executed with each negative signal edge To execute a...

Page 13: ...a 5 V to 24 V signal must be permanently applied to the EN input If a 5 V to 24 V signal is applied to the STEP input a clockwise rotation is executed at the pre set speed To execute a counter clockwi...

Page 14: ...SET 1 Top Hat rail mounting clip with matching screw Connectors D7 CONNECTOR SET Complete set off all dryve D7 connector plugs 8 Service Customer service de dryve igus net 49 0 2203 9649 845 Technical...

Reviews: