background image

General Information

900004-00Q, 10/2018

Innovative Hearth Products
DRT2000 and DRC2000 Direct-Vent Fireplaces

8

INSTALLATION

PACKAGING

All models include 

The assembled vented gas fireplace heater is packaged with:

•  Literature Kit (envelope in bottom compartment containing Installation and Operation Instructions (this manual),  

Hot Glass Safety Flyer, and Safety-In-Operation Warning Labels)

•  U-Shaped Vent Restrictor (attached to Literature Kit envelope)

•  Hood (Inside firebox)

Traditional models also include

•  Log Set (packaged in a carton inside the firebox)

•  Volcanic Stone—1 bag (in bottom compartment)

•  Glowing Embers—1 bag (in bottom compartment)

Contemporary models also include

•  Glass Media

•  Contemporary Burner Panel

INTRODUCTION

These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential and 

commercial applications.
Millivolt fireplaces have a millivolt gas control valve with piezo ignition system. If a blower will be installed, electrical 

power must be provided at the time of fireplace installation.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is 

required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide 

backup power for fireplace operation (excluding the optional blower).
NOTE: Installation and repair should be done by a qualified service person. The fireplace should be inspected before 

use and at least annually by a professional service person. More frequent cleaning may be required due to excessive 

lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air 

passageways of the fireplace be kept clean.

Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire 

l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. 

Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité 

importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les 

conduits de circulation d’air de l’appareil soient tenus propres.

NOTE: Diagrams and illustrations are not necessarily shown to scale.

Approved Vent Components

These fireplaces are designed, tested and listed for operation and installation with the following vent components 

only:
•  Secure Vent

®

 Direct-Vent System Components,

•  Secure Flex

®

 Flexible Vent Components, and 

• Z-FLEX

®

 Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada 

Limited.

Use only the correct size venting (4-1/2” inner and 7-1/2” outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent 

components with these fireplaces.

Codes and Standards

These fireplaces comply with National Safety Standards and are tested and listed by PFS Corporation (Report No. 

F13-094) to ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas 

fireplace heaters.
These fireplaces are listed for installation in bedrooms and manufactured homes.
The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54—latest edition (In Canada, the current CAN/CGA-B149.1 installation code).
The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the 

absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical 

Code, CSA C22.1—latest edition.

Summary of Contents for Superior Fireplaces DRT2000 Series

Page 1: ...rvice des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou par le fournisseur de gaz INSTALLER Leave this manual with the appliance CONSU...

Page 2: ...DRIO CALIENTE CAUSAR QUEMADURAS USTED NUNCA DEBE TOCAR EL VIDRIO CALIENTE LOS NI OS NUNCA DEBE TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact...

Page 3: ...se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el v...

Page 4: ...nds Mantels 15 Installation Preparation 15 Installation Installation Sequence 16 Construct the Fireplace Framing 16 Prepare the Fireplace Top Spacers 18 Route the Gas Supply Line to the Fireplace 18 V...

Page 5: ...subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un...

Page 6: ...Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide poison...

Page 7: ...isable to have an alternate primary heat source when installed in a dwelling Your gas appliance is covered by a limited 20 year warranty You will find a copy of the warranty accompanying this manual P...

Page 8: ...ace be kept clean Remarqu L installation et la r paration devrait tre confi es un technicien qualifi L appareil devrait faire l objet d une inspection par un technicien professionnel avant d tre utili...

Page 9: ...C 3 23 kPa Table 3 Inlet Gas Supply Pressure Fuel Pressure Natural Gas 3 5 WC 0 87 kPa Propane 10 0 WC 2 49 kPa Table 4 Manifold Gas Supply Pressure Test gauge connections are provided on the front of...

Page 10: ...es and Regulations 248 C M R Sections 4 00 through 8 00 Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector us...

Page 11: ...re uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locating television sets and decorative plants B...

Page 12: ...H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flashing 1 25 4 mm minimum clearance to combustibles...

Page 13: ...he combustion air inlet to any other fireplace 6 150 mm for fireplaces 10 000 Btu h 3 kW 9 230 mm for fireplaces 10 000 Btu h 3 kW and 50 000 Btu h 15 kW 12 300 mm for fireplaces 50 000 Btu h 15 kW 6...

Page 14: ...l width and depth of the unit The fireplace may be located on or near conventional construction materials However if installed on combustible materials such as carpeting vinyl tile or other combustibl...

Page 15: ...305 10 254 8 203 6 152 4 102 2 51 in mm 8 203 10 254 12 305 14 356 16 406 18 457 Hood Fireplace Mantel depth Wall Finishes Surrounds Mantels NOTE Combustible wall finish materials and or surround mat...

Page 16: ...Verify Proper Fireplace Operation Page 40 Finishing 14 Optional Install the Firebox Liners Page 41 15 Traditional Fireplaces Install the Logs Volcanic Stone and Glowing Embers Page 41 16 Contemporary...

Page 17: ...t View Left Side View Right Side View E F G H J K L M Blower access panel Hood Junction box access Gas line access N O Model E F G H door J K L M N O 33 Models 30 1 8 765 26 1 4 667 18 3 8 467 30 1 2...

Page 18: ...lace framing Pipe coupling recommended 5 1 4 140 mm 3 77 mm Proper Sizing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be ins...

Page 19: ...Figure 33 5 Install the blower control switch according to its included instructions 6 Place the Fireplace in the Framing and Secure NOTE Nailing flanges combustible members and screw heads in areas...

Page 20: ...r vertical Baffle from top retain screws but discard baffle Reinstall screws to seal holes after vertical baffle is removed Discard the vertical baffle Step 8 Remove the 2 screws holding the block off...

Page 21: ...um horizontal run 60 ft Maximum vertical run 60 1 9 25 Horizontal Distance ft Vertical Height ft Vertical Height ft 2 5 Elbow 5 10 15 Base wing Base 6 ft Minimum vertical run 6 ft Minimum vertical run...

Page 22: ...ed a 6 x 1 2 screw can be used at the joint but is not required as the pipe will securely lock when twisted Figure 17 Where required a telescopic vent section SV4 5LA may be used to provide the instal...

Page 23: ...5 0 6 186 15 5 0 0 0 0 4 4 196 5 16 375 0 1 0 0 4 5 207 17 25 0 0 0 6 0 6 211 5 17 625 1 0 0 6 0 7 217 5 18 125 0 1 0 6 0 7 229 5 19 125 0 0 1 6 0 7 232 5 19 375 0 0 0 0 5 5 241 5 20 125 0 0 0 7 0 7 2...

Page 24: ...s specified in ANSI Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the gas...

Page 25: ...nt pipe on Page 22 6 Install firestop spacer at ceiling When using Secure Vent use SV4 5VF firestop spacer at ceiling joists when using Secure Flex use SF4 5VF firestop spacer If there is living space...

Page 26: ...at top and sides only and trim where necessary Seal the top and both sides of the flashing with waterproof caulking 12 Install the storm collar Install the storm collar supplied with the flashing ove...

Page 27: ...here an elbow is the only vertical component in the system WARNING Do NOT join separate sections of concentric flexible vent pipe Figure 25 Top Vent Straight Table 16 Rear Vent One 90 Elbow Ceiling fi...

Page 28: ...run with more than 6 ft of vertical rise See Page 21 for more information If 25 ft of H horizontal vent run is needed then 5 ft straight section minimum of V vertical vent will be required This table...

Page 29: ...tain the minimum clearances for combustibles Page 24 2 Frame the exterior wall opening Locate the center of the vent outlet on the exterior wall Table 11 Cut and or frame an opening 10 1 2 x 12 1 8 26...

Page 30: ...gure 27 13 Install the firestop spacer at the exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacer over the opening at the exterior side of t...

Page 31: ...ent of Vent Run Sections Relative to Exterior Surface of Framing Last Vent Section Use Telescopic Vent Section SV4 5LA If Necessary Adaptor SV4 5RCH Use silicone caulking to seal the top and sides of...

Page 32: ...near level Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary NOTE SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used any time ven...

Page 33: ...age 21 for more information Compact termination SV4 5HTKCT shown See Table 21 as an aid in venting component selection for a particular range of exterior wall thicknesses If 25 ft of H horizontal vent...

Page 34: ...cure Flex use ceiling firestop spacer SF4 5VF When using Secure Flex use wall firestop spacer SF4 5HF Wall firestop spacer SV4 5HF Ceiling firestop spacer SV4 5VF H V H1 H2 Table 27 Top Vent Three 90...

Page 35: ...flexible vent then push it back out of the way b Apply a bead of Mill Pac Black 700 F high temperature sealant P N 10K81 to the inner adaptor collar approximately 1 2 from the end c Pull and extend t...

Page 36: ...Secure Flex vent to Secure Flex terminations only Do NOT substitute Secure Vent terminations or Secure Vent adaptor for Secure Flex components Secure Flex termination and adaptor collars are a differ...

Page 37: ...ADAPTOR HOT NEUTRAL OPTIONAL GROUND BATTERY HOLDER DFC WIRE HARNESS SPARK WIRE CABLE PILOT GROUND WIRE PILOT SENSOR CABLE HOOD IGNITER ROD FLAME SENSOR PILOT TUBE CPI SWITCH OFF O INTERMITTENT PILOT M...

Page 38: ...nction box 4 Connect the black power supply wire to the lower outlet s red pigtail lead Figure 33 Connect the white power supply wire to the outlet s common terminal 5 Connect the ground supply wire t...

Page 39: ...it according to the installation instructions provided with the kit NOTE The tab connecting the receptacles of the outlet box must be broken in FBK 100 and FBK 200 blower kit applications Figure 33 12...

Page 40: ...pen flame to check for leaks Turn on gas supply and test for gas leaks using a gas leak test solution also known as bubble leak solution NOTE Using a soapy water solution is an effective leak test sol...

Page 41: ...due to sooting resulting from improperly setting the air shutter is not covered under the warranty The air shutter rod and nearby appliance surfaces are hot Exercise caution to avoid injury while adju...

Page 42: ...f air shutter is open too far Flame will be blue Air shutter gap should be decreased Figure 38 Air Shutter Adjustment Rod Air Shutter Adjustment Rod Down Fully Open Position Burner Tube Adjustment Rod...

Page 43: ...All models must have a barrier installed prior to operation 1 Open the control compartment door Page 50 2 Hold the barrier in front of the glass door and slide it up into the slots above the glass do...

Page 44: ...ollez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r sidence...

Page 45: ...ption The following flashing comes packaged with a storm collar 77L78 SV4 5F Flat Roof Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4...

Page 46: ...with 48 1219 mm compressed flex H1969 SF4 5HT 2 Horizontal Square Termination for flex without flex 77L87 SFKIT12S Square Term for flex with 12 305 mm compressed flex 77L88 SFKIT18S Square Term for f...

Page 47: ...e bon fonctionnement de l appareil converti n a pas t v rifi selon les instructions du fabricant fournies avec la trousse Le fournisseur de service qualifi ayant r alis l installation assume les respo...

Page 48: ...ted by carbon monoxide than others including pregnant women people with heart or lung disease or anemia those under the influence of alcohol and those at high altitudes NOTE Do not place furniture or...

Page 49: ...opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea F...

Page 50: ...te switch wall switch remote control rocker switch or wall thermostat and the pilot is lit the fireplace main burner can be turned ON OFF using the optional switch Burn in Period The first few times t...

Page 51: ...h an electronic gas valve have a continuous pilot ignition CPI switch installed in the control compartment This switch allows the pilot to be switched from intermittent mode to continuous mode Intermi...

Page 52: ...rding to these instructions improper combustion could occur This could result in the excessive production of soot and or the colorless odorless toxic gas carbon monoxide CO NOTE If applicable install...

Page 53: ...ilot flame is not obstructed See Verifying Appliance Operation on Page 39 1 If necessary remove the glass door Page 56 Locate and bend up Burner Locating Tabs Figure 47 2 Locate the log placement brac...

Page 54: ...If necessary remove the glass door Page 55 2 Locate the log placement brackets not all are shown Figure 51 Figure 51 Placing log 1 Figure 52 Placing logs 2 and 3 Glowing Embers Do not place glowing e...

Page 55: ...installed AVERTISSEMENT Une barri re con ue pour r duire le risque de br lure par le hublot chaude est fournie avec l appareil et doit tre install WARNING The door should easily close without needing...

Page 56: ...annel with the flat side toward the fireplace then swinging the base of the barrier into the brackets and lowering it into place 5 Close the control compartment door Removing the BARRIER 1 Open the ac...

Page 57: ...components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodically during the...

Page 58: ...lable at your local IHP dealer Never attempt to paint a hot fireplace Do not attempt to repaint the fireplace until the finish is completely cured Burn in Period on Page 50 If the surface becomes stai...

Page 59: ...er Page 70 Cleaning the burner Carefully remove the logs media Vacuum out any foreign matter on the burner e g lint carbon etc Ensure the burner ports are free of debris NOTE Improper positioning of l...

Page 60: ...signs of dislocation of the vent components Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection procedure detailed in this manual Replacing Glowing Embers Ho...

Page 61: ...switch 80L86 FBK 250 Blower Variable Speed with thermal snap switch Glowing Embers and Volcanic Stone Glowing Embers and Volcanic Stone Catalog Model Description 88L53 FGE Bag of Glowing Embers 80L42...

Page 62: ...S STAT Wall control Catalog Number Large LCD display Shows room and set temperatures in F and C Wall mounted Thermostatic or manual ON OFF operation Connects to wall switch wire H8864 Model WS S TSTA...

Page 63: ...00 blower kit is installed Variable Speed Wall Switch Kit Catalog Model 045571H VSWS ACCESSORY COMPONENTS continued Termination Guard Kits The vent termination guards may be used to minimize exposure...

Page 64: ...mmediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call...

Page 65: ...mm diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicie...

Page 66: ...y gas control which has been under water Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may ha...

Page 67: ...ur peut avoir une batterie de secours installer les batteries au besoin 8 Placez l interrupteur du r cepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bo...

Page 68: ...lighting instructions a Defective pilot generator thermocouple Check pilot flame it must impinge on thermocouple Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the...

Page 69: ...k the gas supply and gas shutoff valves b Loose wires to the valve or ignition module Check control compartment for any obviously loose wiring call a service technician if necessary c Pilot flame is n...

Page 70: ...1 Millivolt Pilot Assembly Liquid Propane 69L18 1 69L18 1 69L18 1 69L18 1 Millivolt Piezo Igniter 10K86 1 10K86 1 10K86 1 10K86 1 Millivolt Piezo Igniter Wire 56L21 1 56L21 1 56L21 1 56L21 1 Millivolt...

Page 71: ...personal injury Homeowner Replacement Parts Description 33 Models 35 Models 40 Models 45 Models Catalog Number Qty Catalog Number Qty Catalog Number Qty Catalog Number Qty 1 Glass Door F1905 1 F1841...

Page 72: ...Operation 900004 00Q 10 2018 Innovative Hearth Products DRT2000 and DRC2000 Direct Vent Fireplaces 72 Back view not representative of all fireplace models 6 3 2 8 4 1 7 5 Figure 48 Replacement Parts...

Page 73: ..._______________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___________________...

Page 74: ...______________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____________________...

Page 75: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Page 76: ...e changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed...

Reviews: