VENTING INSTALLATION
Continued
Pitch
Slope Opening "A"
Max.
Used Flashing
Model No.
Flat
0°
15"
V6F-8DM
0-6/12
26.6°
16
1
/
8
"
V6F-8DM
6/12- 12/12
45.0°
20
3
/
8
"
V12F-8DM
Figure 14 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM OR V12F-8DM)
Determine flashing to be used with roof opening chart. Slide flashing
over pipe until base is flat against roof. Replace as many shingles as
needed to cover exposed area and flashing base. Secure in position
by nailing through shingles (see Figure 15). DO NOT NAIL THROUGH
FLASHING CONE.
Installing Flashing on a Metal Roof
When installing flashing on a metal roof, it is required that putty tape
be used between flashing and roof. Flashing must be secured to roof
using #8 x 3/4" screws and then sealed with roof coating to prevent
leakage through screw holes. A roof coating must also be applied
around perimeter of flashing to provide a proper seal.
Figure 15 - Flashing Installation
Storm Collar Installation (SC1)
Place storm collar over pipe and slide down until it is snug against
open edge of flashing (see Figure 16). Use SC1 for all round termina-
tions. Apply waterproof caulk around perimeter of collar to provide
a proper seal.
Figure 16 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with listed round top or chase
terminations. In any case, refer to installation instructions supplied
with termination. Terminations approved for this fireplace are RT-8DM
and RLT-8DM that can be used for flashing or chase and ET-8DM,
ETO-8DM, ETL-8DM and ETLO-8DM for chase style termination only.
Figure 17 shows an RLT-8DM round top termination.
CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
Terminations with 16" slip pipe sections are available. RTT-8DM and
RLTT-8DM are approved for flashing installations. When needed,
these adjustable terminations may be used in combination with pipe
assembly to achieve correct chimney height.
Note:
In the rare instance there is a problem with side driven rain or
wind or chimney is not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
Figure 17 - Termination
30"
(76.2 cm)
Minimum Measurements
Opening "A"
14
3
/
8
"
(48.3 cm)
1"
(2.54
cm)
1"
(2.54
cm)
1"
(2.54 cm)
Nail Only Outer
Perimeter of
Flashing
Storm Collar
Underlap
Shingles at
Bottom
Flashing Cone
Overlap Shingles
Top and Sides Only
Chimney Pipe
Waterproof Caulk
Storm Collar
Flashing
Attach Bracket
Tabs to Outer Pipe
(3 Places) Secure
with Screws
RLT-8DM
Level of Flue
Gas Outlet
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
Overlap Shingles
Top and Sides
Flue Pipe of RLT-8DM
Inside Inner Pipe of
Chimney