Quick programming using Avelour
Installation guide
K0J00121
IJINUS - 25 ZA de Kervidanou 3, 29300 MELLAC - France - – Customer Service: +33 2 98 09 03 32 /
9
If the current is converted in water height, three more parameters can be set:
1. Calibration:
a calibration of the connected sensor is possible to put an offset on the converted height
measurement
2. Flowrate / Volume:
it is possible to convert the height measurement into a flowrate measurement. To
calculate the flowrate, a relationship between the water height and the flowrate must be indicated in the
logger. To do so, a table should be created by clicking in the "Edit table" button to have the possibility to
create the table by clicking on the "Edit table" button.
With the flowrate, two calculation of the volume accumulation can be done and recorded in the logger:
periodic (hourly, daily or monthly) and/or infinite.
3. Sampler enslaving:
If the flowrate calculation has been set, it is possible to enslave a sampler with the
open-drain output. The enslaving volume can be adjusted and a verification of the good relationship
between the logger and the sampler can be verified by clicking on the "Launch" button.
Five enslaving conditions are available: none, height over a high level threshold (mm), height under a low
level threshold (mm), flow over a high level threshold (m3/s), flow under a low level threshold (m3/s).