4000 Series Programmable Pushbutton Lock
25
Troubleshooting & Technical Support
?
A deleted User access code is accepted—unlocks the lock.
➔
A user with the identical access code exists in another User Group.
☞
Ensure that duplicate access codes do not exist across Groups.
?
When a valid access code is entered, the lock unlocks but it
alternately flashes the green and red lights during the
unlock time period instead of just the green light.
➔
This is the low battery indicator. The lock batteries are weakening;
however, the lock will continue to operate for up to 2 000 openings
after the first warning.
☞
Replace all four AA alkaline batteries with new batteries.
?
No sound is heard from the lock when access codes are
entered—when a pushbutton is pressed or access is granted.
➔
The lock buzzer sound is set to off.
☞
Program the lock buzzer sound to loud (command code 702) or soft
command code 701) as desired.
For Technical Support, call 800 849 8324
or (336) 725 1331
(Winston-Salem, NC U.S.A.) from 8:00 AM to 5:00 PM Eastern time,
Monday to Friday (except holidays).
4000 Series Programmable Pushbutton Lock
24
Troubleshooting &
Technical Support
Chapter 7
?
Problem
➔
Possible cause
☞
Solution
?
The lock does not respond at all—no lights and no sound—
when a key is pressed.
➔
1. The connector end of the ribbon cable connecting the front-housing
and the inside-housing is not snugly pushed in.
☞
Push in the connector so that it locks snugly and makes a good
connection.
➔
2. The batteries are missing, the battery connector is not connected,
one or more batteries are placed with the wrong polarity, the batteries
are completely discharged, or non-alkaline batteries are in use.
☞
Correct the above condition and retry.
➔
3. The lock is currently in tamper shut-down mode.
☞
To open the lock, use the mechanical override key, press the hard-wired
remote-unlock switch (if enabled), or simply wait until the tamper
shutdown time period (30 seconds to 15 minutes) has elapsed.
?
A User access or Service access code is not accepted—will not
unlock the lock.
➔
The access code is not programmed into the lock.
☞
Program the lock to add the access code.
?
The lock can be opened without an access code.
➔
The lock is in passage mode.
☞
Program the lock to disable the passage mode (command code 400),
if desired.