DIGIOHMpro
- 12 -
•
Connect one test tip to the designated common conductor. Then touch with
the second test tip a conductor, then another conductor etc. DIGIOHMpro
always displays the number of conductor corresponding to the numbered
terminal of the DIGIsort on the opposite end.
Important notices for proper function of the DIGISORT function
- The presence of voltage on the conductors is indicated by the "Uin" message
on the display. In this case, immediately disconnect the transmitter DIGIsort –
risk of damage!
- The length of conductor > 300 m, too high capacitance, high induced voltage
etc. may cause malfunction of the DIGISORT function!
3.5. Other functions of the instrument
Illumination of measurement point with white LED
LED can be switched on/off by briefly pressing and releasing the
START
key.
Note: The test tips have to be without applied voltage.
3.6. RESET of the instrument
If the device does not operate as described in this manual, we recommend
RESET: disconnect both test tips from tested object and turn off the instrument.
It the proper function is not restored after turning on the instrument, than turn it
off again, remove batteries (the procedure is described in chapter 4.1), wait at
least 10 seconds, and then insert them into the instrument again.
If problems persist, e.g. a spontaneous shutdown of the instrument, flickering of
the display, malfunction of control keys etc., insert a new fully charged NiMH
batteries, or new high quality alkaline batteries.
If the instrument measures the voltage and if resistance is not measured, check
the fuse, which is located under the batteries / fuse compartment cover. See
chapter 4.1 for instructions how to do it.
If the instrument still does not work properly, put the instrument out of operation,
remove batteries (the procedure is described in chapter 4.1), secure it against
any unintended operation and contact your distributor or service.