Table of Maximum Suggested Operating Voltages and Model Wire Colors 

DELTA  or  WYE 

Nominal 

System Voltage 

2Nx 

Model  

Voltage Code 

Phase 

To 

Phase 

Phase 

To 

Ground 

Phase Leg  #1 

Wire 

Color 

Phase Leg  #2 

Wire 

Color 

    Ground 

     Wire 

     Color 

 
 
 

110, 120, 125 

2N1 

132 V 

132 V 

Black 

Black 

    Green 

 

208, 220, 230, 240, 250 

2N2 

264 V 

264 V 

Black 

Black 

    Green 

 

305, 347, 380 

2N3 

418 V 

418 V 

Black 

Black 

    Green 

 

450, 460, 470, 480 

2N4 

528 V 

528 V 

Black 

Black 

    Green 

 

525, 575   /   600 

2N5  /  2N6 

660 V 

660 V 

Black 

Black 

    Green 

 

INSTALLATION STEPS  (

NOTE:  Only ONE LED is used for 2Nx models)

   

STEP 1:

  Check Voltages 

 

Confirm that the nominal system voltage does not exceed the maximum suggested operating voltage for the model to be installed according to the Table above.  All 
voltage  measurements  should  be  completed  with  a  RMS  voltmeter.    DO  NOT  INSTALL  THE  FUSED  UNIT  IF  THE  MEASURED  VOLTAGE  EXCEEDS  THE 
MAXIMUM SUGGESTED OPERATING VOLTAGE OF THE DEVICE.

 

CAUTION:  Do not proceed further until power has been removed from the electrical system. 

STEP 2:  

Mounting the Unit 

Non-lug type SPDs are provided with 18-24 inches of #10 AWG/TEW stranded wire.  For best performance, mount the SPD so that all wires can be cut and connected in 
the shortest, straightest path possible, the goal being 6 inches of wire length or less. For every inch of conductor longer than 6-inches, you increase the let-through voltage 
of the SPD by 21.7 volts for an ANSI/IEEE Category B, 6kV, 3kA impulse. 

 

No sharp bends should be made in the installation.  If bends are unavoidable, make them smooth and flowing.  The device contains no position-dependent 
components; therefore, the device can be mounted upside down or sideways. 

 

Do not cut any wires until suppressor has been mounted. Units with plastic hubs must be installed with the non-metallic flexible conduit and extra hub. 

 

While holding the SPD on the wall, determine the shortest, straightest distance between the hub on suppressor and hub to be installed on panel.  Cut the flexible 
conduit to shortest length possible to fit securely over both hubs. 

 

Twist the trimmed flexible conduit onto the extra hub.  Slide conduit and hub over wires of the SPD and twist the conduit onto the hub of the SPD. 

 

  Connect the extra hub to the panel and mount the SPD to the wall.

 

STEP 3:  

Connecting “Optional Form C” Dry Relay Contacts       (Applies only to SPDs with optional Dry Relay Contacts) 

 

Make sure power is removed from surge suppressor.

 

 

Open surge suppressor lid and note encapsulant height prior to drilling or punching enclosure.  (Allow internal clearance for locknuts).

 

 

Drill 0.5” diameter clearance hole through side, top or bottom of unit and install a watertight strain relief (i.e.: Altech #225-A00 (Part No. SR011).

 

 

NOTE:   

Surge  suppressor  is  equipped  with  two  sets  of  contacts.    The  first  set  (labeled  1  &  2,  N/C)  is  normally  closed  and  the  other  set  (labeled  3  &  4,  N/O)  is 

normally open with power applied. 

 

Contacts are rated at 60 W (from 30 VDC @ 2 A to 150 VDC @ 0.4 A) or 100 VA (from 50 VAC @ 2 A to 220 VAC @ 0.45 A). 

 

Alarm contacts accept AWG #26 (0.14mm

2

) to AWG #16 (1.5mm

2

) wire.  Wire size must be in compliance with NEC/CEC, State or Local codes for power on circuit.  

Follow rules for the class of wiring used when routing alarm leads.  To maintain NEMA-4 (IP66) rating use appropriate cable and watertight strain relief. 

 

Connect alarm circuit(s) to Normally Open (N/O) or Normally Closed (N/C) terminals as required. 

 

Upon replacing front cover of suppressor, certain models allow variour lid rotations (90° to 180°) for improved label orientation. (model specific)

 

STEP 4:

  Wire the SPD into the Electrical System 

 

Carefully lay out the wires keeping them as short and straight as possible.  (Wires may be slow-twisted together thereby reducing RF-impedance.) After a satisfactory 
layout has been made to the appropriate termination points as described below, cut the wires and connect them as instructed. 

 

Connect the GREEN ground wire from the SPD  to the system ground bus bar or to a lug mounted in the can or frame close to the SPD if the Ground bus bar is not 
close following the current NEC/CEC.  

Refer to earlier sections for systems utilizing an isolated ground. 

 

Connect the phase wires or “hot” wires (see table above for wire colors) from the SPD to the phase conductors or buses of the electrical system through the required 
circuit  interrupts  (fuses  or  breakers)  described  above.    Note  that  the  SPD  has  internal  fusing  and  does  not  require  external  circuit  interrupts  (external  fuses  or 
breakers).  The Phase conductors may be directly connected to the phase conductors or buses after the main disconnect. 

 

Upon replacing front cover of suppressor, certain models allow various lid rotations (90° or 180°) for improved label orientation (< model specific). 

Before energizing, measure the voltage again to ensure it is within the levels in the table above. 

Immediate failure of the SPD will occur if installed on voltages higher than shown in the Table at the top of this page.

 

STEP 5:

  Apply Power to the Surge Suppressor 

 

The LED should be illuminated.  If not, remove power from the SPD and contact Surge Suppression, LLC, at:  1-(888)-987-8877.  

 