Ilumen
9
Installation Manual Ilumen PID Box Mini v1.3
9)
Turn the DC switch from the inverter back on followed by the AC side of the PV plant
9
D
ECOMMISSIONING THE
I
LUMEN
PID
S
OLUTION
Switch off the Ilumen PID Box Mini. Disconnect the Ilumen PID Box Mini from the AC grid. Wait
for minimum 20 minutes. Make sure the AC cannot be plugged in again. Disconnect the DC
switch from the inverter and wait until it is discharged. Disconnect all DC connectors going to
the PV arrays and then disconnect the lines going to the inverter. When all electrical connections
are disconnected you can dismount the Ilumen PID Box Mini.
10
T
ROUBLESHOOTING
10.1
N
O GOOD
PID
REGENERATION
If the modules are not regenerating or not regenerating fast enough you should check following
things:
Control the grounding of the system. If necessary you should place additional
interconnections.
Is the Ilumen PID Box Mini properly connected to the grid?
Is the DC power supply properly connected (is its indication light burning)?
Let an expert check if the problem you’re having with the yield is caused by PID