2. Hold the PDU in the side of the rack cabinet, and attach the vertical mounting
brackets to the side braces with four M6 screws and nuts that come with the
PDU.
Notes:
a. Leave enough space to connect, route, and disconnect power cords.
b. If you are installing a cable-management bracket in the same side of the
rack cabinet, leave enough space between the outlet side of the PDU and
the EIA mounting flanges for the cable-management bracket installation.
Attention:
You must disconnect the main input power before you connect or
disconnect the input power cord from the PDU.
3. If the PDU comes with a detached power cord, connect the power cord. Align
the connector on the power cord that comes with the PDU with the connector
on the front of the PDU, turning as necessary for key alignment; then, turn the
twist-lock on the connector clockwise until it locks into place.
Key alignment
Twist lock
Chapter 2. Installing the PDU vertically in a rack cabinet
13