You must use clip nuts to install the mounting brackets. Clip nuts come with the
PDU and are installed on the rack mounting flanges, as shown in the following
illustration.
21
20
19
To install the PDU in the 1 U mounting space in the side of an IBM Enterprise rack
cabinet, complete the following steps:
1. Align the vertical-mounting brackets to the front of the PDU. Make sure that you
attach the brackets so that the power outlets face the rear of the rack cabinet.
LA
N
3
4
1
2
5
6
2. Attach the brackets to the PDU with two M3 x 5 screws per bracket. Use the
screws that come with the PDU.
16
DPI C13 PDU+, DPI C13 3-phase PDU+, DPI C19 PDU+, and DPI C19 3-phase PDU+: Installation and Maintenance Guide