Chapter 8. PDU specifications
The following table contains the product specifications of the PDUs. The PDUs in
the following list correspond by number to the rated voltages, maximum power
ratings, and power cords that are listed in the table:
1. DPI 32 amp/250 V 1-phase Enterprise C13 PDU+ with IEC 309 2P+N+Gnd
connector
2. DPI 60 amp/208 V 1-phase Enterprise C13 PDU+ with IEC 309 2P+Gnd
connector
3. DPI 63 amp/250 V 1-phase Enterprise C13 PDU+ with IEC 309 2P+N+Gnd
connector
4. DPI 32 amp/250 V 3-phase Enterprise C13 PDU+ with IEC 309 3P+N+Gnd
connector
5. DPI 30 amp/208 V 1-phase Enterprise C13 PDU+ with Nema L6-30P
connector
6. DPI 60 amp/208 V 3-phase Enterprise C13 PDU+ with IEC 309 3P+Gnd
connector
7. DPI 60 amp/208 V 1-phase Enterprise C19 PDU+ with IEC 309 2P+Gnd
connector
8. DPI 63 amp/250 V 1-phase Enterprise C19 PDU+ with IEC 309 2P+N+Gnd
connector
9. DPI 32 amp/250 V 3-phase Enterprise C19 PDU+ with IEC 309 3P+N+Gnd
connector
10. DPI 60 amp/208 V 3-phase Enterprise C19 PDU+ with IEC 309 3P+Gnd
connector
Height
43.9 mm (1.73 in.)
Width
447 mm (17.6 in.)
Depth
350 mm (13.78 in.)
Additional clearance
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
Weight (not including power cord)
6.3 kg (13.8 lb)
Weight of power cord (approximate,
varies by PDU model)
5.4 kg (11.8 lb)
Operating temperature at 0 - 914 m
(0 - 3000 ft) (room ambient)
10°- 35°C (50°- 95°F)
Operating temperature at
914 -2133 m
(3000 - 7000 ft) (room ambient)
10°- 32°C (50°- 90°F)
Operating humidity
8 - 80% (noncondensing)
Localized air temperature in PDU
60°C (140°F) maximum
© Copyright IBM Corp. 2006, 2013
51