2. PRODUCT OPERATION
2.1. Global operation
IMPORTANT NOTE :
adeunis® use the most significant byte first format.
PARK MODE
PRODUCTION MODE
SHUT-DOWN
(no battery)
COMMAND MODE
Battery replaced
The product has several operating modes:
2.1.1 PARK mode
The product is delivered in PARK mode, it is in standby mode and its consumption is minimal. To switch the product out of the Park* Mode pass
a magnet across it for a duration higher than 5 seconds. The green LED illuminates to indicate the detection of the magnet and then flashes
quickly during the product starting phase.
The device then sends its configuration and data frames.
2.1.2 COMMAND mode
This mode allows the user to configure the registers of the product.
To enter in this mode, plug the micro-USB cable and use the IoT configurator or AT command. Exit from command mode is done when USB is
disconnected or with an ATO command. The product will return in its previous state, PARK or PRODUCTION.
2.1.3 PRODUCTION mode
This mode allows the user to operate the product in its finale use.
2.1.4 Low battery management
When the product detect that the battery is not able to deliver the level of power required for a emission (extreme temperature or end-of-life of
the battery), it waits to be able to transmit. If it detect that the generated delay is longer than 1 minute, it informs the user activating the “low
Command send-
ing by serial link
Presence of a magnet
on the product >5s
Information sent if
battery low
Auto adaptation
(cf Low battery
management)
The product have
to sent a frame
Product wait
to be able to
transmit
The product
send the frame
Delay lower
than 1 minute
?
“low battery”
appeared in
status byte
Enough pow-
er to send a
frame ?
battery” flag in the status byte of each frame sent.
The “battery low” flag is automatically disappearing when the battery is replaced or when temperature conditions are favorable to the proper
yes
yes
no
no
no
no