Conto D4 - Pd
Programmable Parameters
1 CodE
Access password
Keep simultaneously pressed the
2 keys
until you display page
Load
Password 1000
and confirm
Page
moves the cursor
Prog
increases/decreases the loaded value
Page + Prog
confirms
2 ModE
Energy count configuration
Mode ASY
Partial energy count always active
Total energy (display
T
)
Total energy (display
P
)
Mode SYn
Partial energy count activated by the closing of the external contact
(C - D terminals)
Total energy (display
T
)
Total energy (display
P
)
Partial energy count no active
Partial energy count active
Mode trf
Energy count with double tariff. Tariff switching with closing of the external
contact
(C - D terminals)
Energy tariff 1 (display )
Energy tariff 2 (display )
Energy Count tariff 1
Energy Count tariff 2
3 tiME
Integration time for average power calculation
Selectable values:
5 – 8 – 10 – 15 – 20 – 30 – 60 minutes
Prog
increases the loaded value
Page
decreases the loaded value
Page + Prog
confirms
4 M-Bus Communication
4.1 Addr
Address number
Selectable values:
1...250
Page
moves the cursor
Prog
increases the loaded value
Page + Prog
confirms
4.2 bAUd
Transmission speed
Selectable values:
300 - 600 - 1200 - 2400 - 4800 – 9600 bit/s
Prog
increases the loaded value
Page
decreases the loaded value
Page + Prog
confirms
4.3 00000000
Secondary Address
Selectable values:
0...99999999
Page
moves the cursor
Prog
increases the loaded value
Page + Prog
confirms