MANCANZA FIAMMA /NO FLAME 

 

 

     

  

 

 

 

(E140901X) 19 di/of 33 

 
 

 

Compare the measured value with the tables described below:: 

STATIC PRESSURE 

VALUE 

MINIMUM PRESSURE 

NOMINAL PRESSURE 

MAXIMUM PRESSURE 

NATURAL GAS 2H 

(G20)

 

[PCI=34,02MJ/Nm

3

17,00 mBar 

20,00 mBar 

25,00 mBar 

NATURAL GAS 2ELL 

(G25)

 

[PCI=29,30MJ/Nm

3

18,00 mBar 

20,00 mBar 

25,00 mBar 

LIQUID GAS 3+ 

(G30)

 

[PCI=45,65MJ/kg] 

20,00 / 25,00 mBar 

28,00-30,00 / 37,00 mBar 

35,00 / 45,00 mBar 

 

Pay attention to the PCI (lower heating power) of the gas in use at your site. The PCI varies 

depending on the gas supplied: to know the PCI gas used to refer to the donor or their institution 

consult the data of the last gas bill. 

3.b CHECK OUTLET PRESSURE (DYNAMIC PRESSURE) 

The 

valve’s output pressure is equivalent to the pressure applied to the nozzles. Consistent with the model of 

car and the type of gas for which it is produced, calibration of the nozzle pressure is preset at the factory. 

The  pressure  regulator  of  the  valves  is  always  sealed  and  no  modification  are  required.  Any  adjustment  of 
the output pressure should be made by the calibration of external devices (external pressure reducers). 

P

in  

MAIN GAS INPUT

 

MAIN GAS OUTLET 

(TO THE NOZZLES)

 

Summary of Contents for MCA 1500

Page 1: ...IFICA E PULIZIA VENTILATORI E PULIZIA CANNA FUMARIA 11 5 CONTROLLI ELETTRICI 12 5 a MCA 12 5 b MCM IM7 PLC 15 6 SE NON SI RISOLVE IL PROBLEMA STORICO ALLARMI 17 Summary 1 CHECKS THE END USER CAN DO BY...

Page 2: ...i controlli descritti nell apposito capitolo Comunicare al tecnico eventuali problemi di approvvigionamento del gas avvenuti nei giorni precedenti alla comparsa dell allarme 2 INTERVENTO SUL POSTO DA...

Page 3: ...TICA PRESSIONE MINIMA PRESSIONE NOMINALE PRESSIONE MASSIMA GAS METANO 2H G20 PCI 34 02MJ Nm 3 17 00 mBar 20 00 mBar 60 00 mBar GAS METANO 2ELL G25 PCI 29 30MJ Nm 3 18 00 mBar 20 00 mBar 60 00 mBar GAS...

Page 4: ...l ugello va fatta seguendo le indicazioni di seguito elencate Spegnere la macchina completamente Chiudere il rubinetto del gas che alimenta il macchinario Aprire il pannello laterale della macchina in...

Page 5: ...damento acceso risultasse inferiore a quella nominale operare le dovute correzioni agendo su i regolatori di pressione esterni alla macchina e valutare la portata delle condotte del gas dal punto di e...

Page 6: ...possono variare ed essere soggetti a modifica senza preavviso da parte di IMESA SPA U M MCA 1500 MCA 1800 MCA 2100 CONSUMO GAS GAS CONSUMPTION kW 22 24 6 26 m3 h G20 2 9 3 3 3 4 Kg h GPL LPG 2 0 2 2...

Page 7: ...nte un condotto di scarico che deve essere opportunamente dimensionato e realizzato a norma di legge Si definisce pertanto ARIA PRIMARIA l aria aspirata all interno del bruciatore che viene miscelata...

Page 8: ...imane accesa e non compare l errore MANCANZA FIAMMA il problema da ricercare nella carburazione gas aria in particolar modo nella tipologia di gas a basso potere calorifico impiegato ad es Aria Propan...

Page 9: ...re 4 c VERIFICA E PULIZIA BRUCIATORI All interno del bruciatore presente il gas mescolato con l aria primaria MCA Per verificare la pulizia interna dei bruciatori necessario chiudere il rubinetto del...

Page 10: ...lato I bruciatori possono essere lavati sotto acqua corrente e soffiati con aria compressa Durante la pulizia dei bruciatori verificare che non siano presenti rotture nella prossimit delle griglie di...

Page 11: ...l intasamento risulti eccessivo il depressore installato nella macchina provveder a spegnere il sistema di accensione del gas Questa anomalia non viene rilevata dalla scheda elettronica con un errore...

Page 12: ...le una sequenza molto rapida di scariche elettriche tra il polo caldo della candela e il polo di massa Il bruciatore si accendono salvo problemi elencati nei precedenti capitoli Il sensore di ionizzaz...

Page 13: ...A IM7 MCA SEGNALI DI CONTROLLO E ANOMALIA RISCALDAMENTO FILO N 0 NEUTRO FILO N 51 SEGNALE DI RISCALDAMENTO 230V MANDATO ALLA CENTRALINA FILO N 42 RESET CENTRALINA DI ACCENSIONE NEUTRO MANDATO ALLA CEN...

Page 14: ...IAMMA IM7 MCA FILO N 0 NEUTRO FILO N 51 SEGNALE DI RISCALDAMENTO 230V MANDATO ALLA CENTRALINA FILO N 42 RESET CENTRALINA DI ACCENSIONE NEUTRO MANDATO ALLA CENTRALINA FILO N 41 SEGNALE DI ALLARME FASE...

Page 15: ...NOMALIA RISCALDAMENTO FILO N 0 NEUTRO FILO N 15 SEGNALE DI RISCALDAMENTO 230V MANDATO ALLA CENTRALINA FILO N 73 RESET CENTRALINA DI ACCENSIONE NEUTRO MANDATO ALLA CENTRALINA FILO N 75 SEGNALE DI ALLAR...

Page 16: ...6 di of 33 CONNESSIONI SU CENTRALINA DI ACCENSIONE IM7 PLC MCM FILO N 0 NEUTRO FILO N 15 SEGNALE DI RISCALDAMENTO 230V MANDATO ALLA CENTRALINA FILO N 42 RESET CENTRALINA DI ACCENSIONE NEUTRO MANDATO A...

Page 17: ...guente 1 TEMP per passare da un parametro al successivo scelta parametro 2 TEMP per accedere al dato il dato inizia a lampeggiare e pu essere modificato oppure per memorizzare e passare al dato succes...

Page 18: ...ibed in the relevant section Communicate to the technical problems of gas supply that occurred in the days prior to the appearance of the alarm 2 INTERVENTION ON SITE BY THE TECHNICIAN When working on...

Page 19: ...r site The PCI varies depending on the gas supplied to know the PCI gas used to refer to the donor or their institution consult the data of the last gas bill 3 b CHECK OUTLET PRESSURE DYNAMIC PRESSURE...

Page 20: ...e the gas valve shown in the figure Open the screw contained in the pressure tap P out using a screwdriver the screw although completely loose can t get out of his socket Connect your pressure gauge m...

Page 21: ...ary corrections by adjusting the pressure regulators outside the machine and assess the capacity of the gas pipes from the main supply point usually the counter until the machine 3 c CHECKING THE PIPE...

Page 22: ...rding to the consumption flow rate of the machine the diameter of the pipeline has to be suitably dimensioned according to the length of the pipe itself The following table shows for example the secti...

Page 23: ...nition and the maintenance of the flame inside the burner The air is sucked from the room where the ironer is present through the fan blower and it is conveyed to the outside through an exhaust duct w...

Page 24: ...ry air intake of the burner Close the primary air intake with the hands as can be seen in the photos and start the machine Start the machine having the certainty that the fan is working and rotates in...

Page 25: ...y a supply of gas not suitable for the type of dryer in use It should not be considered a permanent solution to apply 4 c BURNERS INSPECTION AND CLEANING Inside the burner the gas is mixed with the pr...

Page 26: ...ent to half the length of the machine on each side The burners can be washed under running water and blown with compressed air While cleaning the burners check that there are no breaks in the vicinity...

Page 27: ...the blockage is too high the depressor installed in the machine will turn off the ignition system of gas This anomaly is not detected by the electronic board with an error visible in the display Ther...

Page 28: ...harge of the spark plug At this juncture it is audible a very rapid sequence of electrical discharges between the pole hot spark plug and ground wire The burner will light up except for the problems l...

Page 29: ...NECTION HEATING CONTROL AND ERROR SIGNAL WIRE N 0 NEUTRAL WIRE WIRE N 51 HEATING SIGNAL 230V SEND TO GAS IGNITION UNIT WIRE N 42 RESET SIGNAL FOR THE GAS IGNITION UNIT SEND TO GAS IGNITION UNIT WIRE N...

Page 30: ...IM7 MCA WIRE N 0 NEUTRAL WIRE WIRE N 51 HEATING SIGNAL 230V SEND TO GAS IGNITION UNIT WIRE N 42 RESET SIGNAL FOR THE GAS IGNITION UNIT SEND TO GAS IGNITION UNIT WIRE N 41 ALARM SIGNAL PHASE SIGNAL COM...

Page 31: ...0 NEUTRAL WIRE WIRE N 15 HEATING SIGNAL 230V SEND TO GAS IGNITION UNIT WIRE N 73 RESET SIGNAL FOR THE GAS IGNITION UNIT SEND TO GAS IGNITION UNIT WIRE N 75 ALARM SIGNAL PHASE SIGNAL COMING FROM THE G...

Page 32: ...MANCANZA FIAMMA NO FLAME E140901X 32 di of 33 CONNECTION TO GAS IGNITION BOX IM7 PLC MCM WIRE N 0 NEUTRAL WIRE WIRE N 15 HEATING SIGNAL 230V SEND TO GAS IGNITION UNIT PR AIR PRESSURE SWITCH...

Page 33: ...tch to the next parameter parameter selection 2 TEMP to access the data the data starts blinking and can be modified or to store and move to the next digit 3 SPEED and SPEED to edit the data WARNING I...

Reviews: