67
67
de
fr
en
nl
scroll
push
push
push
Select an available BrainCube No.
The BrainCube No. selected must be the same as the «NS sender BrainCube»
No. in the Info menu on the Pleno (
:
page 58)
scroll
push
push
push
Select an available BrainCube No.
If a BrainCube No. is already assigned, it no longer appears in the selection list.
Start-up
Option - BrainCube with ComCube DCD
Up to four BrainCube controls can be operated with one or more ComCube DCD communication modules. Besides the cabling
work (
:
electrical connection page 63), the following parameter settings are required on the BrainCube.
• Open *ComCube*
menu
: press
menu
, then press
esc
+
push
at the same time,
• Make the settings in the *ComCube* menu:
ComCube
BrainCube
off
The selected BrainCube No. indicated.
ComCube
Enable BrainCube for ComCube operation
BrainCube
1
BrainCube
2
BrainCube
3
BrainCube
4
Back
Exit the *ComCube* menu
:
page 58
menu
Display Link-up information
:
ComCube Installation | Operation
Option - BrainCube with ComCube DCA
For the building management system, PIS pressure can be made available in the form of a galvanically isolated 4-20 mA
signal through the ComCube DCA (
:
electrical connection page 63). Parameter settings must not be made on the
BrainCube. PIS 4-20 mA signal conversion is provided by the customer.
PIS pressure sensor
Measurement range
Signal
Pleno PI 6.1 | PI 6.2 | PI 9.1
0–10 bar
→
4-20 mA
:
ComCube Installation | Operation
Water make-up through RS 485-1 interface
The Pleno can be networked through the RS 485-1 interface to receive water make-up signals from the Transfero and
Compresso TecBoxes and switch the water make-up accordingly. Besides the cabling work (
:
electrical connection pages
62–63), the following parameter settings are required on the BrainCube of the sender (Compresso, Transfero):
• Open *ComCube* menu: press
menu
, then press
esc
+
push
at the same time,
• Make the settings in the *ComCube* menu:
ComCube
BrainCube
off
The selected BrainCube No. indicated.
ComCube
Enable BrainCube for parallel operation
BrainCube
1
BrainCube
2
BrainCube
3
BrainCube
4
Back
Exit the *ComCube* menu
:
page 58
menu
Display Link-up information
Summary of Contents for Pleno PI 6.1
Page 25: ...25 25 de fr en nl...
Page 49: ...49 49 de fr en nl...
Page 73: ...73 73 de fr en nl...
Page 97: ...97 97 de fr en nl...
Page 98: ...98...