1.9  SYSTEM FILLING.

Once the boiler is connected, proceed with 

system filling via the filling valve (Fig. 2-2). 

Filling is performed at low speed to ensure 

release of air bubbles in the water via the boiler 

and heating system vents. The boiler has a built-

in automatic venting valve on the circulator. 

Open the radiator vent valves. Close radiator 

vent valves when only water escapes from them.

Close the filling valve when the boiler pressure 

gauge indicates approx. 1.2 bar.

N.B.:

 during these operations start up the 

circulation pump at intervals, acting on the main 

switch positioned on the control panel. 

Vent the 

circulation pump by loosening the front cap and 

keeping the motor running.

Tighten the cap after the operation.

1.10 GAS SYSTEM START-UP.

To start up the system, make reference to the 

Standard: This divides the systems and therefore 

the start-up operations into three categories: new 

systems, modified systems, re-activated systems. 

In particular, for new gas systems:

- open windows and doors;
- avoid presence of sparks or open flames;
- bleed all air from the pipelines;
-  check that the internal system is properly sealed 

according to specifications.

1.11 BOILER START-UP (IGNITION).

To issue the required Declaration of Conformity, 

the following must be performed for boiler 

start-up:

-  check that the internal system is properly sealed 

according to the regulations in force;

-  make sure that the type of gas used corresponds 

to boiler settings;

-  switch the boiler on and check correct ignition;
- make sure that the gas flow rate and relevant 

pressure values comply with those given in the 

manual (par. 3.16);

- check the correct ventilation of the rooms;
- check the existing draught during normal 

functioning of the appliance, e.g. a draught 

gauge positioned at the exit of the appliance 

combustion products;

-  check that there is no backflow of combustion 

products into the room, even during 

functioning of fans;

- ensure that the safety device intervenes in the 

event of gas supply failure and check the relative 

intervention time;

- check activation of the main switch located 

upstream of the boiler.

The boiler must not be started up even if only 

one of the checks should be negative.

Fig. 1-7

Head available to the system.

1.12 CIRCULATION PUMP.

The boilers are supplied with a built-in circulation 

pump with 3-position electric speed control.

The boiler does not operate correctly with the 

circulation pump on first speed. 

To ensure optimal boiler operation, in the case 

of new systems (single pipe and module) it is 

recommended to use the pump at maximum 

speed. The circulation pump is already fitted 

with a capacitor.

Pump release.

 If, after a prolonged period of 

inactivity, the circulation pump is blocked, 

unscrew the front cap and turn the motor shaft 

using a screwdriver. Take great care during this 

operation to avoid damage to the motor.

1.13 KITS AVAILABLE ON REQUEST.

• System cut-off valves kit (on request). The 

boiler is designed for installation of system 

interception cocks to be placed on flow and 

return pipes of the connection assembly. This 

kit is particularly useful for maintenance as 

it allows the boiler to be drained separately 

without having to empty the entire system.

• Zone system kit (on request). If the heating 

system is to be divided into several zones 

(max. 

three),

 in order to interlock them with separate 

adjustments and to keep water flow rate high 

for each zone, Immergas supplies zone system 

kits by request. 

• Polyphosphate dispenser kit (on request). 

The polyphosphate dispenser reduces the 

formation of lime-scale and preserves the 

original heat exchange and domestic hot water 

production conditions. The boiler is prepared 

for application of the polyphosphate dispenser 

kit.

The above-mentioned kits are supplied complete 

with instructions for assembly and use.

Flow rate (l/h)

H

ea

d (kP

a)

  A  =  Head available to the system at 

maximum speed with by-pass 

excluded.

  B  =  Head available to the system at 

maximum speed with by-pass 

inserted.

  C  =  Head available to the system 

at second speed with by-pass 

excluded.

  D  =  Head available to the system 

at second speed with by-pass 

inserted.

Ci

rcu

la

to

r p

um

p a

bs

or

be

d p

ow

er (

W

)

Summary of Contents for 3.018921

Page 1: ...NIKE MINI 28 KW SPECIAL Instruction and warning booklet 1 040845ENG...

Page 2: ...as boilers As for the other issues related to boiler installation e g safety in the work site environment protection injury prevention it is necessary to comply with the provisions specified in the re...

Page 3: ...l heating system pressure 12 2 9 System draining 12 2 10 Anti freeze protection 12 2 11 Case cleaning 12 2 12 Decommissioning 12 3 Boiler start up initial check 13 3 1 Hydraulic diagram 13 3 2 Wiring...

Page 4: ...ies personal responsibility and invalidates the warranty Installation regulations theseboilerscannotbeinstalledinbedrooms studio flats and bathrooms They also cannot be installed in rooms with wood or...

Page 5: ...type used in the boiler which must comply with the regulations in force as insufficient levels can reduce generator output and cause malfunctions Ensure correct gas cock connection by following the m...

Page 6: ...ergas chrono thermostats are connected with 2 wires only Carefully read the user and assembly instructions contained in the accessory kit On Offdigitalchrono thermostat Thechrono thermostat allows set...

Page 7: ...dangerous situations for the user The flue ducts must be connected to the chimney or flue in the same room in which the appliance is installed or at most in the adjoining room and must comply with the...

Page 8: ...intervenes in the eventofgassupplyfailureandchecktherelative intervention time check activation of the main switch located upstream of the boiler The boiler must not be started up even if only one of...

Page 9: ...safety thermostat 6 Fumes hood 7 Delivery probe 8 Safety thermostat 9 System expansion vessel 10 Combustion chamber 11 Boiler circulator pump 12 3 bar safety valve 13 By pass 14 Three way valve motor...

Page 10: ...onnected parts with easily flammable substances Never leave containers or flammable substances in the same environment as the appliance It is prohibited and dangerous to obstruct the air intake even p...

Page 11: ...tacts resistance block LEDs 2 and 7 flash at the same time 04 Parasite flame block LEDs 1 and 7 flash at the same time 20 Loss of remote control communication LEDs 2 and 3 flash alternately 31 Insuffi...

Page 12: ...ure via the valve located at the bottom of the boiler Fig 2 2 N B close the valve after the operation If pressure values reach around 3 bar the safety valve may be activated In this case contact a pro...

Page 13: ...he exit of the appliance combustion products check that there is no backflow of combustion products into the room even during functioning of fans ensure activation of all adjustment devices seal the g...

Page 14: ...ent interventions of the over heating safety thermostat It can depend on reduced water pressure in the boiler little circulation in the heating system the blocked pump or an anomaly of the boiler P C...

Page 15: ...perations must be carried out by a qualified technician e g After Sales Technical Assistance Service Burner adjustment must be carried out using a U or digital pressure gauge connected to the gas valv...

Page 16: ...tables Heating output The boiler is produced and calibrated in the central heating phase at nominal output Permanent reduction of the timer The boiler has an electronic timing device that prevents the...

Page 17: ...with boiler in standby the function activates every 18 hours after the last boiler check power supply In case of functioning in domestic hot water mode the self check starts within 10 minutes after t...

Page 18: ...anel 4 towards you taking care to remove the 2 fixing screws 5 3 16 HEAT OUTPUT N B gasflowratesrefertoheatingpowerbelowa temperature of 15 C and a pressure of 1013 mbar Burner pressure values refer t...

Page 19: ...3994 Domestic hot water adjustable temperature C 38 77 Domestic hot water circuit flow limiter l min 11 Domestic circuit min pressure dynamic bar 0 3 Domestic hot water circuit max working pressure ba...

Page 20: ...Model Cod Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat in...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...Europe S r o 059051 Poprad Matejovce SK Tel 421 524314311 Fax 421 524314316 IMMERGAS SPA ITALY CERTIFIED COMPANY UNI EN ISO 9001 2015 Design manufacture and post sale assistance of gas boilers gas wat...

Reviews: