background image

13

1-10

1-11

1-12

C

13

1-13

5

4

3

1

2

1

2

3

4

5

6

C

13

C

13

C

13

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

1.11 CONCENTRIC HORIZONTAL KIT 

INSTALLATION.

Type C configuration, sealed chamber and 

fan assisted.

The position of the terminal (in terms of dis-

tances from openings, overlooking buildings, 

floor, etc.) must be in compliance with the 

regulations in force.
This terminal is connected directly to the outside 

of the building for air intake and flue exhaust. The 

horizontal kit can be installed with the rear, right 

side, left side or front outlet. For installation with 

frontal outlet, one must use the fixing plate and 

a concentric bend coupling in order to ensure 

sufficient space to carry out the tests required 

by law upon commissioning.
•  External grid. Both the Ø 60/100 and Ø 80/125 

intake/exhaust terminal, if properly installed, is 

pleasant to look at on the outside of the build-

ing. Make sure that the external silicone wall 

sealing plate is properly inserted in the wall. 

 

N.B.:

 for proper system operation the terminal 

with grid must be installed correctly ensuring 

that, the "high" indication on the terminal is 

observed during installation.

Horizontal intake-exhaust kit Ø 60/100 

Kit 

assembly (Fig. 1-10): install the bend with flange 

(2) on the central hole of the boiler, positioning 

gasket (1) with the circular projections down-

wards in contact with the boiler flange, and 

tighten using the screws present in the kit. Fit 

the Ø 60/100 (3) concentric terminal pipe with 

the male side (smooth) to the female side of the 

bend (2) up to the end stop; making sure that the 

internal and external wall sealing plate have been 

fitted, this will ensure sealing and joining of the 

elements making up the kit.
• Extensions for Ø 60/100 horizontal kit (Fig. 

1-11). The kit with this configuration can be 

extended up to a 

max. 12.9 horizontal m

 in-

cluding the terminal with grid and excluding 

the concentric bend leaving the boiler. This 

configuration corresponds to a resistance factor 

of 100. In this case the special extensions must 

be requested.

Immergas also provides a Ø 60/100 simplified 

terminal, which in combination with its exten-

sion kits allows you to reach a maximum exten-

sion of 11.9 metres.

Horizontal intake-exhaust kit Ø 80/125 

Kit 

assembly (Fig. 1-12): to install the kit Ø 80/125 

one must use the flanged adapter kit in order 

to install the flue system Ø 80/125. Install the 

flanged adaptor (2) on the central hole of the 

boiler, positioning gasket (1) with the circular 

projections downwards in contact with the boiler 

flange, and tighten using the screws contained in 

the kit. Engage the bend (3) with the male side 

(smooth) to the end stop on the adapter (1). Fit 

the Ø 80/125 (5) concentric terminal pipe with 

the male side (smooth) to the female side of the 

bend (4) (with lip seals) up to the end top; making 

sure that the internal (6) and external wall sealing 

plate (7) have been fitted, this will ensure sealing 

and joining of the elements making up the kit.
• Extensions for horizontal kit Ø 80/125 (Fig. 

1-13). The kit with this configuration can be 

extended up to a 

max. length of 32 m

, includ-

ing the terminal with grid and excluding the 

concentric bend leaving the boiler. If addi-

tional components are assembled, the length 

equivalent to the maximum allowed must be 

subtracted. In this case the special extensions 

must be requested.

The kit includes:

N° 1 -  Gasket (1)

N° 1 -  Concentric bend Ø 60/100 (2)

N° 1 -  Int./exhaust concentric terminal Ø 60/100 (3)

N° 1 -  Internal wall sealing plate (4)

N° 1 -  External wall sealing plate (5)

The adaptor kit includes:

N° 1  -  Gasket (1)

 N° 1  -  Adaptor Ø 80/125 (2)

The Kit Ø 80/125 includes:

N° 1  -  Concentric bend Ø 80/125 

a 87° (3)

 N° 1  -  Int./exhaust concentric termi-

nal Ø 80/125 (4)

 N° 1  -  Internal wall sealing plate (5)

 N° 1  -  External wall sealing plate 

(6)

The remaining kit components must 

not be used

Max. 12900 mm)

Max. 12790 mm)

Max. 32000 mm)

Max. 31956 mm)

Summary of Contents for 3.025615

Page 1: ...MAGIS VICTRIX ERP IE Instruction and recommendation booklet 1 038946ENG...

Page 2: ......

Page 3: ...fessionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions...

Page 4: ...2 5 Using the boiler 24 2 6 Troubleshooting 25 2 7 Parameters and information menu 27 2 8 Boiler shutdown 28 2 9 Restore central heating system pressure 28 2 10System drainage 28 2 11Anti freeze prot...

Page 5: ...damaged if the safety valve intervenes with an obstructed conveying system the safety valve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contr...

Page 6: ...be followed scrupulously regarding the percentage neces sary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollu tion class o...

Page 7: ...escopic fitting 3 4 R RHT MHT M N 1 Rubber fitting for condensate drainage SC N 1 Condensate drainage corrugated pipe SC N 1 Extension for filling valve N 1 Filling valve N 1 Condensation collection t...

Page 8: ...ecial pickling or descaling products to remove any deposits that could compromise correct boiler operation A chemical treatment of the thermal system wa ter is required in compliance with the technica...

Page 9: ...r is made using wires with a minimum section of 0 50 mm2 and maximum section of 2 5 mm2 and with a maximum length of 50 metres External temperature probe electrical con nection Theboileronlyworksifiti...

Page 10: ...pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning the gaskets black for green ra...

Page 11: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Page 12: ...ent in the kit positioning the relevant gaskets Engage the 90 80 bend with the male end smooth in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it run a...

Page 13: ...orizontal m in cluding the terminal with grid and excluding the concentric bend leaving the boiler This configurationcorrespondstoaresistancefactor of 100 In this case the special extensions must be r...

Page 14: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Page 15: ...th the male side smooth in the female side of the bend 5 up to the end stop ensuring that the internal and external wall sealing plates are fitted Fit the exhaust pipe 9 with the male side smooth to t...

Page 16: ...ical data The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a...

Page 17: ...th is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in ex haust two 90 80 bends on the boiler outlet 1 16 CONFIGURATION TYPE B OPEN CHAMBER AND FAN ASSISTED FOR INDOORS The appli...

Page 18: ...ns featured on the boiler active upon initial ignition and on the heat pump see relative instructions booklet Vent the boiler circulation pump by loosening the front cap and keeping the motor running...

Page 19: ...level from a minimum one to a maximum one by turning the selector switch clockwise in the relative power scale Proportional head program P V 3 fig 1 25 This allows the pressure level head to be propo...

Page 20: ...functioning characteristics of the boiler thanks to its inspectionable filter Kit with two motorised areas on request In the event one wants to divide the thermal sys tem in two areas to interlock the...

Page 21: ...on module 14 Manual air vent valve 15 Negative signal pressure point 16 Positive signal pressure point 17 Sample points air A flue gas F 18 Flue safety thermostat 19 Heat exchanger safety thermal fuse...

Page 22: ...d to weathering rain sunlight etc the appliance power cable must not be re placed by the user if the cable is damaged switch off the ap pliance and solely contact an authorised company to replace it i...

Page 23: ...fter a request for domestic hot water or central heating in order to evacuate residual flue gas F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heatin...

Page 24: ...ting stage if the water temperature is sufficient to heat the system the boiler can operate just with the activation of water circulation Winter operation mode with room central heating with boiler 2...

Page 25: ...on circuit or anomaly in the flame control unit Press the Reset button 1 2 23 Return probe anomaly The board detects an anomaly on the system return NTC probe The boiler does not start 1 2 24 Push but...

Page 26: ...g and cooling are inhibited Check the type of anomaly directly on the remote panel display see relative instruc tions manual In the event the heat pump does not fea ture any anomaly check that the dom...

Page 27: ...ntenance chapter By turning the central heating temperature se lector switch 3 scroll through the menu items By pressing button D access the various levels of the menu and the choice of parameters is...

Page 28: ...Victrix ErP series boiler features an anti freeze function that lights the burner automatically when the temperature falls below 4 C standard protection up to minimum tem perature of 3 C All informat...

Page 29: ...omestic hot water check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where provided If even only a single safety check offers a negative result do n...

Page 30: ...re point 22 Flue sample point 23 Fumes hood 24 Heat exchanger safety thermal fuse 25 Delivery probe 26 Safety thermostat 27 Ignition electrodes 28 Burner 29 Condensation module cover 30 Return probe 3...

Page 31: ...tle water circulation in the system or blocked pump Check on the manometer that the system pressure is within established limits Check that the radiator valves are not closed and also the functionalit...

Page 32: ...in the table Par 3 20 3 6 CALIBRATION OF NUMBER OF FAN REVS Attention verification and calibration is neces sary in the case of transformation to other types of gas in the extraordinary maintenance ph...

Page 33: ...ating selector switch to maxi mum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling probe to the...

Page 34: ...efines the maximum flow tempera ture corresponding to operation with minimum external temperature see graph Fig 1 5 it can be set between 50 C and 85 C N B to continue one must confirm the parameter p...

Page 35: ...to automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 09 L M 12 L M and 15 L M operation with defined flow AUTO RELAY1 RELE1 0...

Page 36: ...event the boiler circulator pump is replaced with a traditional fixed speed circulator pump one must connect the new circulator pump to the relay board P76 15 C 14 C CE With S34 On If the reading of...

Page 37: ...HEATING OPERATION IN COMBINATION WITH THE HEAT PUMP Following a request during the room heating mode the electronics decide according to the external temperature whether to activate the heat pump or w...

Page 38: ...han that set by the do mestic hot water selector switch SET the boiler does not switch on 3 18 YEARLY APPLIANCE CHECK AND MAINTENANCE The following checks and maintenance should be performed at least...

Page 39: ...screws 11 disassemble the front 1 of the boiler by loos ening the screw 2 by 1 4 turn push the front upwards while pulling it towards you at the same time to release it from the side 3 and upper 4 ho...

Page 40: ...17200 2 16 3 48 35 5 1 61 3 40 34 7 1 58 4 54 46 3 19 0 16340 2 05 3 17 32 3 1 53 3 10 31 6 1 50 4 15 42 4 18 0 15480 1 94 2 87 29 3 1 45 2 81 28 6 1 42 3 79 38 7 17 0 14620 1 84 2 59 26 5 1 37 2 53...

Page 41: ...ss at casing with burner On Off 80 60 C 0 49 0 70 Heat loss at flue with burner On Off 80 60 C 0 02 1 90 Central heating circuit max operating pressure bar 3 Maximum heating temperature C 90 Adjustabl...

Page 42: ...r N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat...

Page 43: ...0 071 kW At partial load elmin 0 010 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 005 kW Emissions of nitrogen oxides NOX 23 mg kWh For mixed central heating appliances St...

Page 44: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Page 45: ...e energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further fac...

Page 46: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Page 47: ...ncy under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxiliary electricity...

Page 48: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038946ENG rev ST 002042 001 06 19 Inglese p...

Reviews: