GENERAL WARNINGS.

All Immergas products are protected with suitable transport 

packaging. 

The material must be stored in a dry place protected from the 

weather.

This instruction manual provides technical information for 

installing the Immergas kit. As for the other issues related to kit 

installation (e.g. safety at the workplace, environmental protection, 

accident prevention), it is necessary to comply with the provisions 

specified in the regulations in force and with the principles of good 

practice.

Improper installation or assembly of the Immergas appliance and/

or components, accessories, kits and devices can cause unexpected 

problems for people, animals and objects. Read the instructions 

provided with the product carefully to ensure proper installation.

Installation and maintenance must be performed in compliance 

with the regulations in force, according to the manufacturer's 

instructions and by professionally qualified staff, meaning staff 

with specific technical skills in the plant sector, as envisioned by 

the law.

GENERALITIES.

An independent mixed zone is added using this kit (second zone) 

for coupling the Trio Pack. Before performing any intervention, 

disconnect the power supply to the installed indoor unit by 

acting on the switch placed upstream from the appliance. 

INSTALLATION ON TRIO PACK (FIG. 1-2).

To install proceed as follows:

-  open the door of the Solar or Domus Container and lock it 

to prevent it from getting in the way during the subsequent 

installation stages;

-  empty the system by acting on the drain fitting (1) placed 

under the accumulation (2). Before draining, ensure that the 

system filling cock is closed;

-  remove the two caps (Part. 3 and 4 Fig. 3) on the accumulation 

(2).

Connect the components of the second zone as described below 

(Fig. 3):

-  assemble the G 3/4 complete fitting (26) on the lower sheet, 

securing it with the lock nut (5) and the washer (22); 

-  assemble the circulator (24) on the fitting, checking the pres-

ence of the gasket (27) and apply the insulation (13); 

-  fit the system return pipe (12) on the lower sheet, securing it 

with the lock nut (5) and washer (22); connect it in the upper 

part to the accumulation (2) interposing the seal gasket (6);

-  assemble the mixing valve (16) on the connection pipe (12) 

interposing the seal gasket (11); 

Attention: respect the orientation of the mixing valve, as 

represented in detail in Fig. 3.

-  Connect the second zone delivery pipe (25) to the mixing valve 

interposing the sealing gasket (11) and to the accumulation 

(2) interposing the sealing gasket (6);

-  pre-mount the safety thermostat (9) with the 2 screws (10) 

and the flow probe (18) on the second zone flow pipe (20);

-- apply the insulation (21) on the connection pipe (20);
-  assemble the complete pipe (20) between the circulator fitting 

(24) checking the presence of the gasket (27) and the mixing 

valve (16) interposing the seal gasket (11)

-  apply the relative insulation (17) to the mixing valve, locking 

it with the 2 clamps in the kit.

apply the IP cover (14) to the three-way motor (15) and as-

semble on the mixing valve, then connect it electrically;

-  assemble the thermometer (7) on the relative bracket by 

connecting the capillary to the system flow pipe (20) and 

fixing it with the clip (19);

-  apply the left shell (8) and the right shell (23) on the circulator, 

locking them with the 2 clamps in the kit;

Connection unit (on request).

The system is dispatched from the factory without the connec-

tion unit. The kit includes the pipes and fittings for connecting 

the pack. It is also possible to select the connection choosing 

between the kit with bottom, rear or side connection. 

Note:

 to preserve the correct functioning of the manifold within 

the hydraulic circuit, it is necessary to install an Y filter, that can 

be inspected and that is contained in the kit, on the zone return.

STARTING THE SYSTEM.

Once the electrical connection stages are completed, restore the 

correct water pressure in the Central heating system using the 

relevant filling valve. Power up the Indoor Unit and check that 

every room thermostat (or remote control) activates the rela-

tive circulator. Bleed the system and the appliance correctly as 

described in the instruction booklet of the installed indoor unit.

Mixing valves initialisation.

Every time that the Indoor Unit is powered, initialisation of the 

mixing valves is carried out, closing them for three minutes. This 

way synchronisation is performed between the P.C.B. and the 

mixing valve. The transfer of heat energy to the mixed zone can 

only take place at the end of this initialisation phase.

Checks.

 

It is recommended to check the maximum flow rate circulating 

in the system in the flow rate/head graphics in order to evaluate 

the correct dimensioning of the design parameters. In addition, 

the latter must also allow a maximum surface temperature of 

the radiating floor that is in compliance with that established 

by Standard UNI EN 1264.

Summary of Contents for 3.031483

Page 1: ...COD 3 031483 KIT AGGIUNTIVO 2a ZONA MISCELATA PER TRIO PACK ADDITIONAL KIT 2nd MIXED ZONE FOR TRIO PACK IT Foglio istruzioni e avvertenze Instruction and warning book IE...

Page 2: ...rientamento della valvola miscela trice come rappresentato nel dettaglio in Fig 3 collegare il tubo di mandata seconda zona 25 alla valvola miscelatrice 16 interponendo la guarnizione di tenuta 11 e a...

Page 3: ...3 2 4 3 1 1 2 Legenda 1 Raccordo di scarico 2 Accumulo 3 Tappo 4 Tappo TRIO PACK IN SOLAR O DOMUS CONTAINER TRIO PACK CON KIT 2A ZONA MISCELATA IN SOLAR O DOMUS CONTAINER...

Page 4: ...x2 12 1 Tubo ritorno impianto seconda zona 13 1 Coibentazione con velcro 14 1 Coperchio motore tre vie 15 1 Motore valvola miscelatrice 16 1 Valvola miscelatrice 17 1 Coibentazione valvola miscelatric...

Page 5: ...e il connettore della sonda di mandata 2 e del termostato sicurezza 3 Collegare il circolatore 5 al connettore 1 Collegare il connettore della valvola miscela trice a 3 vie 4 N B avvolgere i raccordi...

Page 6: ...a bassa temperatura M10 2 Circolatore zona 2 M31 2 Valvola miscelatrice zona 2 1 Chiuso 2 Comune 3 Aperto 4 Pannello principale Legenda codici colori BK Nero BL Blu BR Marrone G Y Verde Giallo GY Grig...

Page 7: ...la possibilit di avere fastidiosi rumori di flusso d acqua nelle condutture nelle valvole e nei radiatori Condizioni ottimali di benessere termico e di benessere acu stico Prevalenza costante P C Il...

Page 8: ...lgimento Avvolgimentodifettoso Lampeggiacon lucerossa Sotto sovratensione Tensionedialimentazionelatoalimentazi onetroppobassa alta Controllarelatensionedireteele condizionid impiego richiedereil Cent...

Page 9: ...70 10 A X1 Y1 Y2 MIN MIN MAX M AX B Prevalenza disponibile all impianto zona 1 diretta velocit fissa Prevalenza disponibile all impianto zona 1 diretta prevalenza proporzionale Legenda A Prevalenza di...

Page 10: ...Y1 Y2 MIN MIN MAX MAX B Prevalenza disponibile all impianto zona 1 diretta prevalenza costante Prevalenza disponibile all impianto zona 2 miscelata velocit fissa valvola miscelatrice aperta Legenda A...

Page 11: ...AX B Prevalenza disponibile all impianto zona 2 miscelata prevalenza proporzionale valvola miscelatrice aperta Prevalenza disponibile all impianto zona 2 miscelata prevalenza costante valvola miscelat...

Page 12: ...alvola unidirezionale 16 Filtro ispezionabile optional 17 Filtro ispezionabile 18 Termostato antigelo 19 Valvola di sicurezza 8 bar 20 Rubinetto di svuotamento bollitore 21 Rubinetto intercettazione v...

Page 13: ...14 Valvola unidirezionale 15 Filtro ispezionabile optional 16 Filtro ispezionabile 17 Termostato antigelo 18 Valvola di sicurezza 8 bar 19 Rubinetto di svuotamento bollitore 20 Rubinetto intercettazi...

Page 14: ...ented in detail in Fig 3 Connectthesecondzonedeliverypipe 25 tothemixingvalve interposing the sealing gasket 11 and to the accumulation 2 interposing the sealing gasket 6 pre mount the safety thermost...

Page 15: ...15 2 2 4 3 1 1 TRIO PACK IN SOLAR OR DOMUS CONTAINER TRIO PACK WITH 2nd MIXED ZONE KIT IN SOLAR OR DOMUS CONTAINER Key 1 Drain fitting 2 Accumulation 3 Cap 4 Cap...

Page 16: ...y thermostat 10 2 Fixing screws 11 3 Gasket 30x22x2 12 1 Second zone system return pipe 13 1 Velcro insulation 14 1 Three way motor cover 15 1 Mixing valve motor 16 1 Mixing valve 17 1 Mixing valve in...

Page 17: ...t Connect the cables in the electrical panel of the Indoor Unit as shown in Fig 5 Lower the wiring coming out of the electri cal panel until it can be secured through the clamps 6 Connect the connecto...

Page 18: ...E7 2 Low Temperature safety thermostat M10 2 Zone 2 pump M31 2 Zone 2 mixing valve 1 Close 2 Common 3 Open 4 Main panel Colour code key BK Black BL Blue BR Brown G Y Green Yellow GY Grey OR Orange W...

Page 19: ...s valves and radiators is eliminated by reducing the head Optimal conditions for thermal comfort and acoustic well being Constant head P C The circulator pump maintains the pressure level head constan...

Page 20: ...ng Itflasheswith redlight Under Overvoltage Feedsidepowersupplyvoltagetoolow high Checkthemainsvoltageandoperating conditions asktheAuthorised TechnicalAssistanceCentre Excessive module tem perature I...

Page 21: ...40 60 80 10 30 50 70 10 A X1 Y1 Y2 MIN MIN MAX M AX B Total head available to the system of zone 1 direct fixed speed Total head available to the system of zone 1 direct proportional head Key A Total...

Page 22: ...80 10 30 50 70 10 A X1 Y1 Y2 MIN MIN MAX MAX B Total head available to the system of zone 1 direct constant head Total head available to the system of zone 2 mixed fixed speed mixing valve open Key A...

Page 23: ...0 50 70 10 A X1 Y1 Y2 MIN MIN MAX MAX B Total head available to the system of zone 2 mixed fixed speed mixing valve open Total head available to the system of zone 2 mixed constant head mixing valve o...

Page 24: ...14 Direct zone circulator 15 One way valve 16 Inspectionable filter optional 17 Inspectionable filter 18 Antifreeze thermostat 19 8 bar safety valve 20 Tank unit draining valve 21 DHW vessel shut off...

Page 25: ...r optional 13 Direct zone circulator 14 One way valve 15 Inspectionable filter optional 16 Inspectionable filter 17 Antifreeze thermostat 18 8 bar safety valve 19 Tank unit draining valve 20 DHW vesse...

Page 26: ...26...

Page 27: ...27...

Page 28: ...ducts that are correctly installed and used with respect to the Standards in force N B correct periodic maintenance is highly recommended Immergas TOOLBOX L App studiata da Immergas per i professionis...

Reviews: