Technical Documentation
Technical Documentation
After the burner has been switched off at the end of any type of request, the combustion
chamber is washed and the fan is kept running for 30 seconds.
Sealed chamber post-ven-
tilation
To prevent the water-gas exchanger from overheating, if the boiler temperature detected
by the NTC central heating probe (B1) exceeds 90 °C, the fan is switched on until the
temperature drops below 85 °C.
Delivery overheating
ventilation
To prevent the water-gas exchanger from overheating, at the end of each central heating, an-
tifreeze or “chimneysweep” request, the circulator (M1) keeps working for 150 seconds.
Post-circulation pump
Breakage of the central heating delivery probe (B1) stops boiler operation.
Breakage of the delivery
NTC probe (B1)
Breakage of the d.h.w. probe (B2) is signalled by the flashing of LED 10 ( ), and the
boiler continues working in the d.h.w. mode.
Breakage of the d.h.w. NTC
probe (B2)
(optional kW X version)