27
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
Id
Parameter
(ref. 17)
Parameter
Description
Range
(ref. 21 Fig.
2-1)
Default
P0
DHW thermostat
Establishes the switch-off method in DHW mode.
1 Correlated: the boiler switches off according to the temperature set.
0 Fixed: the switch-off temperature is fixed at the maximum value regardless of the value
set on the control panel.
0 - 1
1
P1
Solar delay
timing
The boiler is set to switch-on immediately after a request. for DHW In the case of coupling
with a solar storage tank positioned upstream from the boiler, it is possible to compensate
the distance between the storage tank and the boiler in order to allow the water to reach
the boiler. Set the time necessary to verify that the water is hot enough (see par. Solar
panels coupling)
0 - 30 seconds
0
P2
Pump function-
ing
The pump can function in two ways.
0 intermittent: in winter "mode" the circulator is managed by the room thermostat or by
the remote control
1 continuous: in "winter" mode the circulator is always powered and is therefore always
in operation
0 - 1
0
P3
Relay 1
(optional)
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0
= Off
1
= Main zone control
2
=General alarm
3
= CH phase active
4
= External gas valve power supply
5
= Aquaceleris PTC control (Do not use on this boiler model)
0 - 5
0
P4
Relay 2
(optional)
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0
= Off
1
=General alarm
2
= CH phase active
3
= External gas valve power supply
4
= Secondary zone control (from TA on relay P.C.B. contact)
0 - 5
0
P5
Relay 3
(optional)
The boiler is set-up for functioning with the relay P.C.B. (optional), which can be
configured
0
= Off
1
= Chiller remote activation
2
=General alarm
3
= CH phase active
4
= External gas valve power supply
5
= Aqua Celeris device PTC control (Do not use on this boiler model)
0 - 5
0
Id
Parameter
(ref. 17)
Parameter
Description
Range
(ref. 21 Fig.
2-1)
Default
t0
Central heating
ignitions timer
The boiler has electronic timing, which prevents the burner from igniting too often in
central heating mode
0 - 600 sec-
onds
18
t1
Central heating
ramp timer
In the ignition phase, the boiler performs an ignition ramp in order to arrive at the
maximum power set
0 - 840
seconds
84
t2
CH ignition de-
lay from TA and
CR request
The boiler is set to switch-on immediately after a request. In the case of particular sys-
tems (e.g. area systems with motorised thermostatic valves etc.) it may be necessary to
delay ignition.
0 - 600 sec-
onds
0
t3
Display lighting
Establishes the display lighting mode.
0 Automatic:
the display lights up during use and dims after 15 seconds of inactivity. In
the event of an anomaly the display flashes.
1 Off:
the display is always lit with low intensity
2 On:
the display is always lit with high intensity.
0 - 2
0
t4
Display
Establishes what indicators 17 and 21 display (Fig. 2-1).
0
Indicator 17: displays the set DHW setting;
Indicator 21: in winter mode it displays the set CH setting, while the indicator is switched
off in summer mode
1
Indicator 17: it is switched off in the presence of a request. Without any request the
indicator shows the set DHW setting.
Indicator 21: in the presence of a request, it shows the instant flow temperature of the
boiler. Without any request in summer mode, the indicator is off. In winter mode it
shows the set CH setting.
0 - 1
1