33
STEMkW Special ed 01/08
EOLO Mini kW Special
Technical Documentation
Technical Documentation
Permanent timing reduction.
The boiler is fitted with an
electronic timer that prevents the burner igniting too frequently
in the central heating phase.
The boiler is supplied with a timer as a standard feature, set
at 180 seconds.
Central heating ignitions timer
(continuous variation)
LED flashing
(slow)
30 seconds
LED 1
55 seconds
LED 2
80 seconds
LED 3
105 seconds
LED 4
130 seconds
LED 5
155 seconds
LED 6
180 seconds (Standard setting)
LED 7
255 seconds
LED 8
Central Heating ramp timing
. The boiler supplies the maxi-
mum output set in the previous parameter.
The boiler executes an ignition ramp of about 650 seconds to
go from minimum to nominal central heating output.
Central heating ignitions timer
(continuous variation)
LED flashing
(slow)
65 seconds
LED 1
130 seconds
LED 2
195 seconds
LED 3
390 seconds
LED 4
455 seconds
LED 5
520 seconds
LED 6
585 seconds
LED 7
650 seconds (Standard setting)
LED 8
Central heating ignitions delayed due to Room thermostat
or Remote control requests (CAR or CRD).
The boiler is set
to turn on immediately after a request.
In the case of particular systems (i.e. zone systems with mo-
torised thermostat valves, etc.) it might be necessary to delay
ignition.
Central heating ignitions delayed due to
Room thermostat or Remote control requests
(continuous variation)
LED flashing
(slow)
0 seconds (Standard setting)
LED 1
54 seconds
LED 2
131 seconds
LED 3
180 seconds
LED 4
206 seconds
LED 5
355 seconds
LED 6
400 seconds
LED 7
510 seconds
LED 8
Domestic hot water thermostat.
If the “correlated” thermostat
is set the boiler switches off according to the temperature set
with the d.h.w. adjustment knob.
While if the “fixed” d.h.w. thermostat is set, switching off
temperature is set at 85°C regardless of what position the
knob is in.
Domestic hot water thermostat
LED flashing
(slow)
Correlated
LED 1
Fixed
(Standard setting)
LED 8
Circulator function.
Two circulator functioning modes can
be selected in the central heating phase.
In the “intermittent” mode, it is activated either by the Remote
control or eventual by the room thermostat, in the “continua-
tive” mode the circulator works all the time when the main
selector switch by Remote control is on heating.
Circulator function
LED flashing
(slow)
Intermittent (Standard setting)
LED 1
Continuous
LED 8
Gas G110 – China Gas.
The setting of this function serves to
adjust the boiler to work with the gases of the first family.
Gas G110 -
China Gas
(first family gas)
LED flashing
(slow)
Off (Standard setting)
LED 1
On
LED 8