16
INS
TALLER
US
ER
MAINTEN
AN
CE TECHNI
CI
AN
1.15 DUCTING OF FLUES OR
TECHNICAL SLOTS.
Ducting is an operation through which by in-
serting one or more relevant pipes, one achieves
a system for the evacuation of the combustion
products of a gas appliance, consisting in the
combination of an existing or new ducting pipe
with a chimney, flue or technical slot (also in new
buildings). Ducting requires ducts declared to
be suitable for the purpose by the manufacturer,
following the installation and user instructions,
provided by the manufacturer and the require-
ments of the standards in force.
1.16 CONFIGURATION TYPE B
22
,
OPEN CHAMBER AND FORCED
DRAUGHT FOR INDOORS.
The appliance can be installed inside buildings in
B
22
mode; in this eventuality, all technical rules
and national and local regulations in force, must
be complied with.
- Type B open chamber boilers must not be
installed in places where commercial, artisan
or industrial activities take place, which use
products that may develop volatile vapours
or substances (e.g. acid vapours, glues, paints,
solvents, combustibles, etc.), as well as dusts
(e.g. dust deriving from the working of wood,
coal fines, cement, etc.), which may be dama-
ging for the components of the appliance and
jeopardise functioning.
- in B
22
configuration, unless otherwise provided
for by local regulations in force: the boilers
must not be installed in bedrooms, bathrooms
or bedsits. They must neither be installed in
rooms containing solid fuel heat generators
nor in rooms communicating with said rooms.
- The installation of appliances in B
22
configura-
tion is only recommended in places that are not
lived in and which are permanently ventilated.
To install them one must use the coverage kit
whose installation is referred to in paragraph
1.11.
1.17 FLUE EXHAUST TO FLUE/CHIMNEY.
Flue exhaust does not necessarily have to be
connected to a branched type traditional flue.
The flue exhaust, for boiler clots installed in C
configuration, can be connected to a special LAS
type multiple flue. For B
22
configurations, exhaust
is only allowed into individual chimney or directly
into the external atmosphere via a relevant terminal,
unless otherwise provided by local regulations.
Multiple and combined flues must be specially
designed according to the calculation method
and requirements of the standards in force, by
professionally qualified technical staff. Chimney
or flue sections for connection of the flue exhaust
pipe must comply with requisites of technical
standards in force.
1.18 FLUES, CHIMNEYS AND CHIMNEY
CAPS.
The flues, chimneys and chimney caps for the
evacuation of combustion products must be in
compliance with applicable standards. Chimneys
and roof-installed exhaust terminals must com-
ply with the outlet height and with the distance
from technical volumes set forth by the technical
standards in force.
Positioning the wall flue exhaust terminals.
The
wall flue exhaust terminals must:
- be installed on external perimeter walls of the
building;
- be positioned according to the minimum di-
stances specified in current technical standards.
Combustion products exhaust of natural
draught or fan assisted appliances in open-top
closed environments.
In spaces closed on all
sides with open tops (ventilation pits, courtyards
etc.), direct combustion product exhaust is
allowed for natural draught or fan assisted gas
appliances with a heat input range from 4 to 35
kW, provided the conditions as per the current
technical standards are respected.
1.19 SYSTEM FILLING.
Once the boiler is connected, proceed with sy-
stem filling via the filling cock (Fig. 2-2).
Filling is performed at low speed to ensure rele-
ase of air bubbles in the water via the boiler and
central heating system vents.
The boiler has a built-in automatic venting valve
on the circulator.
Check if the cap is loose.
Open
the radiator vent valves.
Close radiator vent valves when only water
escapes from them.
Close the filling valve when the boiler pressure
gauge indicates approx. 1.2 bar.
N.B.
: during these operations turn on the circula-
tion pump at intervals, by means of the stand-by
button located on the control panel.
Vent the
circulation pump by loosening the front cap and
keeping the motor running.
Screw the cap back on after the operation.
1.20 GAS SYSTEM START-UP.
To start up the system, make reference to the
Standard:
In particular, for new gas systems:
- open windows and doors;
- avoid presence of sparks or naked flames;
- bleed all air from pipelines;
- check that the internal system is properly sealed
according to the regulations in force.
1.21 BOILER START UP (IGNITION).
To commission the boiler (the operations listed
below must only be performed by qualified per-
sonnel and in the presence of staff only):
- check that the internal system is properly sealed
according to the regulations in force;
- ensure that the type of gas used corresponds to
boiler settings;
- Check that there are external factors that may
cause the formation of fuel pockets;
- switch the boiler on and ensure correct ignition;
- make sure that the gas flow rate and relevant
pressure values comply with those given in the
manual ( Par. 3.15);
- ensure that the safety device is engaged in the
event of gas supply failure and check activation
time;
- check activation of the main switch located
upstream from the boiler;
- check that the intake and/or exhaust terminals
(if fitted) are not blocked.
The boiler must not be started up even if only
one of the checks should be negative.
Summary of Contents for EOLO STAR 24 5E
Page 1: ...EOLO STAR 24 5E IE Instructions and warning book 1 040471ENG ...
Page 2: ......
Page 33: ......
Page 34: ......
Page 35: ......