Error
Code
Anomaly signalled
Cause
Boiler status / Solution
27
Insufficient circula-
tion
This occurs if there is overheating in the boiler due to insufficient water
circulating in the primary circuit; the causes can be:
- low system circulation; check that no shut-off devices are closed on
the heating circuit and that the system is free of air (deaerated);
- circulating pump blocked; free the circulating pump.
If normal conditions are restored the boiler
restarts without having to be reset (1).
28
Domestic hot water
leakage
If during the heating phase, a rise in domestic hot water temperature
occurs, an anomaly is signalled and heating temperature is reduced
to limit the formation of limescale in the heat exchanger.
Check that all domestic hot water system
cocks are closed and are not drawing and
check also that there are no leaks in the
system. Once good conditions are restored
in the domestic hot water system, the boiler
returns to normal functioning (1)
31
Loss of remote control
communication.
This occurs if an incompatible remote control is connected, or if
communication between the boiler and the remote control is lost.
Disconnect and reconnect the power to the
boiler. If the Remote Control is not de-
tected on re-starting the boiler will switch
to “Summer” local operating mode. In this
case, the controls on the control panel of
the boiler are enabled again (1).
36
IMG BUS communi-
cation loss
Communication loss on the IMG BUS protocol
The boiler does not satisfy the room heating
requests (1).
37
Low power supply
voltage
This occurs when the power supply voltage is lower than the allowed
limits for the correct boiler operation.
If normal conditions are restored the boiler
restarts without having to be reset (1).
38
Loss of flame signal
This occurs when the boiler is ignited correctly and the burner
flame switches off unexpectedly; a new attempt at ignition is
performed and if normal conditions are restored, the boiler does
not have to be reset.
Note:
when attempting ignition, the minimum heat output of
the boiler increased to a maximum of two consecutive ignitions;
the minimum heat output conditions are reached once again,
as per gas valve calibration, following the "P.C.B. PERIODIC
AUTO-VERIFICATION" function or simply disconnecting the
power supply to the boiler.
(1).
43
Block due to loss of
flame signal
This occurs if the ''Flame signal loss (38)'' error occurs many times
in a row within a preset period.
Press the Reset button (1).
44
Block for exceeding
the maximum ope-
nings close to the gas
valve
This occurs if the gas valve remains open for longer than required
for normal operation, without
the boiler switching on.
Press the Reset button (1).
59
Supply voltage fre-
quency anomaly
The board detects a main supply voltage frequency anomaly.
The boiler does not start (1).
80
Block - gas valve
driver issue
- This occurs in the event of malfunctions of the P.C.B. that controls
the valve.
Press the Reset button (1).
85
Afterburner problem
block
Potential gas valve, electrode or P.C.B. problem.
Press the Reset button (1).
98
Block - maximum no.
of software errors
The maximum number of software errors possible has been reached. Press the Reset button (1).
(1) If the shutdown or fault persists, contact an authorised company (e.g. Technical After-Sales Service).