Attention:
if during the adjustment phase, the
boiler nominal heat output value is exceeded by
0.2 mbar (table para. 3.15) you must exit and
re-enter from the calibration step to rerun the
adjustment.
• Adjustment of boiler minimum thermal heat
output.
- Press button (3) or (4) to select parameter b01
(minimum boiler heat output during D.H.W.).
Note:
only proceed after having calibrated the
boiler nominal heat output.
- Press the button (5) to increase the thermal
power and button (6) to decrease it. After the
adjustment, press and hold the reset button
(1) to save the parameter. Confirmation that
the parameter has been saved is given by the
value flashing.
- Adjust the boiler nominal heat output in hea-
ting phase (para. 3.7 parameter “P5”).
- Adjust (eventually) the maximum heating
power (para. 3.7 parameter “P6”).
Calibration correction.
The procedure described below allows the para-
meters set with the "Complete calibration" and
the default ones to be partially changed.
Access the valve calibration function.
Note:
there must be no D.H.W. demand to access
the gas valve calibration function.
If parameter P15 has recently been set to 5 (e.g.
for full gas valve calibration), a different value
must be set to access the "Calibration correc-
tion" or simply cutting-out the power supply
to the boiler.
• Correction of boiler nominal heat output cali-
bration.
- Press buttons (2) and (5) simultaneously for 5
seconds until ''Ma'' + "nu" appears alternately
on the display.
Note:
press buttons (2) and (5) again for 5 se-
conds or wait 2 minutes without implementing
any adjustment to exit from the calibration
correction phase.
- Wait until the parameter b02 appears
(adjustment of the boiler nominal heat output).
Note:
the boiler starts up in heating mode; if
you wish to adjust the D.H.W., open a hot water
tap after the burner goes on.
- Adjust parameter b02, observing the maximum
pressure values stated in the tables (Para. 3.15)
depending on the type of gas.
- Press the button (5) to increase the thermal
power and button (6) to decrease it. After the
adjustment, press and hold the reset button
(1) to save the parameter. Confirmation that
the parameter has been saved is given by the
value flashing.
• Correction of boiler minimum heat output
calibration.
- Press button (3) or (4) to select parameter b01
(minimum boiler heat output during D.H.W.).
- Press the button (5) to increase the thermal
power and button (6) to decrease it. After the
adjustment, press and hold the reset button
(1) to save the parameter. Confirmation that
the parameter has been saved is given by the
value flashing.
- Adjust the boiler nominal heat output in hea-
ting phase (para. 3.7 parameter “P5”).
- Adjust (eventually) the maximum heating
power (para. 3.7 parameter “P6”).
3.7 PROGRAMMING THE P.C.B.
The boiler is prepared for possible programming
of several operation parameters. By modifying
these parameters as described below, the boiler
can be adapted according to specific needs.
To access the programming phase, proceed as
follows (references Fig. 2-1):
- press buttons (1) and (2) for 5 about seconds
until the programming mode is accessed on
the display;
- Using keys (3) and (4), select the parameter to
be changed indicated in the following table:
- adjust the corresponding value consulting the
table using keys (5) and (6): first pressure of
buttons displays the current value;
- confirm the value set by pressing the Reset but-
ton (1) for about 5 seconds. Only the displayed
value is saved.
Note:
2 minutes after no button is touched
will automatically cancel the operation or by
pressing buttons (1) and (2) simultaneously for
about 5 seconds. Modified but not confirmed
values are to be restored to the value preceding
the modification.