3.8 "CHIMNEY SWEEP” FUNCTION.
When activated, this function forces the boiler
at max. output (P06) for 15 minutes.
In this state all adjustments are excluded and
only the temperature safety thermostat and the
limit thermostat remain active (temperature is
limited by the parameter “P12”). To activate the
chimney sweep function, press the Reset key for
at least 5 seconds. Its activation is indicated by
the flashing symbols (8 and 11 Fig. 2-1). This
function allows the technician to check the
combustion parameters. After the checks disable
the function, switching the boiler off and then on
again or simply by pressing the reset button for
about 5 seconds (1 Fig. 2-1).
The maximum heating power can be set to P06
and P05 by pressing buttons (3 or 4). The power
can be adjusted by one percentage point by
pressing buttons (5 or 6).
If you wish to run the "chimney sweep" function
in D.H.W., open a D.H.W. tap after switching
the burner on.
Attention:
ensure a sufficient DHW flow, in
order to avoid high temperatures of the water.
The maximum boiler power can be set to 0% and
100% by pressing buttons (3 or 4). The power can
be adjusted by one percentage point by pressing
buttons (5 or 6).
Note:
the display of the boiler power percentage
alternates with the display of the temperature
read by the flow probe.
3.9 PUMP ANTI-BLOCK FUNCTION.
In the “summer” functioning mode ( ) the
boiler has a function that starts the pump at least
once every 24 hours for 30 seconds in order to
reduce the risk of the pump becoming blocked
due to prolonged inactivity.
In the “winter” functioning mode ( ) the boiler
has a function that makes the pump start at least
once every 3 hours for 30 seconds.
3.10 DOMESTIC HOT WATER CIRCUIT
ANTI-EXTRUDER FUNCTION.
This function reduces the heating temperature
to 57°C if the domestic hot water circulation is
detected in the heating mode. The function can
be enabled using parameter (P3).
3.11 RADIATORS ANTIFREEZE
FUNCTION.
If the system return water is below 4°C, the boiler
starts up until reaching 42°C.
3.12 P.C.B. PERIODICAL SELF-CHECK.
During functioning in central heating mode or
with boiler in standby, the function activates
every 18 hours after the last boiler check/power
supply. In case of functioning in domestic hot wa-
ter mode the self-check starts within 10 minutes
after the end of the withdrawing in progress, for
duration of approx. 10 seconds.
NOTE:
during self-check, the boiler remains off,
including signalling.
Id
Parameter
Parameter
Description
Range
(ref. 9 Fig. 2-1)
Default
P18
Display lighting
Establishes the display lighting mode:
00 = (Off) the display lights on if buttons are pressed (time out = 15 seconds).
01 = (Auto) equal to 00, it also lights on to indicate the flame presence.
02 = (On) always on.
00 - 02
01
P19
Flow off tempera-
ture increase
(Central heating)
Increases the flow off temperature at ignition only in the first 30 seconds.
on - oF
on